Air-Cooled Models—Self-Contained Compressor

30

Figure 16 General arrangement—Air-cooled models with digital scroll and fan speed control

Inverted Trap * on
discharge line to
extend above base
of coil by a minimum
of 7-1/2" (190mm)

Condenser
Coil

Schrader
Valve

Fusible
Plug

Traps* every
25 ft. (7.6m)
of rise

Evaporator
Coil

Expansion
Valve

Solenoid
Valve

Sight
Glass

Filter
Dryer

Liquid Return

Shutoff*
Valve

Sensing
Bulb

External Equalizer

Service
Valves

Hot Gas
Discharge

Check Valve

FACTORY PIPING
FIELD PIPING

*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.

Digital
Compressor

Digital
Solenoid Valve

DPN001726