Introduction

3

1.0

I

NTRODUCTION

1.1

System Descriptions

Challenger 3000

environmental control systems are available in three main system configurations:

• self-contained system with a scroll compressor in the room unit
• self-contained chilled water system
• split system with an evaporator section and a remote condensing unit

All three types are available in upflow or downflow configurations. The standard upflow configuration

is front return. All models require three-phase power. Units are available in 208, 230, 460, or 575V,

60Hz; and 200, 230 or 380/415V, 50Hz.
The following features are included as standard in all room units regardless of the type of system: Lie-

bert iCOM control, A-frame coil (V-frame on upflows), infrared humidifier, finned tubular stainless

steel electric reheat, 2" filter, individual high voltage fused protection and fan assembly.

1.1.1 Self-Contained Systems

Air-Cooled Models

Complete refrigeration system including hot gas bypass and crankcase heater with standard scroll

compressor, standard condenser and fan speed control for 95°F (35°C) ambient at sea level. Optional

Digital scroll compressor with unloading solenoid valve is also available. Digital scroll compressor

systems do not include hot gas bypass.

Water-Cooled Models

Compete refrigeration system including hot gas bypass with standard scroll compressor, water/glycol-

cooled condenser and two-way water regulating valve with bypass. Optional digital scroll compressor

with unloading solenoid valve is also available. Digital scroll compressor systems use a 2-way motor-

ized ball valve in lieu of the regulating valve; they do not include hot gas bypass.

Glycol-Cooled Models

The water-cooled model as described above plus pump package and 95°F (35°C) design ambient dry-

cooler.

GLYCOOL Models (5-Ton Only)

Complete refrigeration system including hot gas bypass with standard scroll compressor, glycol con-

denser and three-way water regulating valve plus an integrally piped Econ-O-Coil with three-way mod-

ulating control valve. Optional digital scroll compressor with unloading solenoid valve is also available.

Digital scroll compressor systems use a 3-way motorized ball valve in lieu of the regulating valve; they

do not include hot gas bypass.

1.1.2 Chilled Water Models

Chilled Water models include chilled water piping, three-way modulating valve, and actuator assem-

bly.