Zone Response Type Definitions

General Information

During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.

Type 00

Zone Not Used

Zone type 00 is used to program a zone that is not used.

Type 02

Entry/Exit Burglary #2

01000-017-V0

Zone type 02 is usually assigned to sensors or contacts on which secondary entry and
exit doors that might be further from the keypad (typically used for a garage, loading
dock, or basement door).

Zone Characteristics:
• Entry delay #2 is programmable from 0-99 seconds (field

36).

• Exit delay is independently programmable from 0-99 seconds (field

34).

• Secondary entry delay, if armed in the AWAY or STAY mode.

• No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.

• Exit delay begins regardless of the arming mode selected.

01000-018-V0

Type 03

Perimeter

Burglary

Zone type 03 is usually assigned to all sensors or contacts on exterior doors and
windows. Zone Characteristics:

Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY mode.

Type 04

Interior, Follower

5890 / 5890PI

01000-019-V1

Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or
hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach
the keypad. It provides an instant alarm if the entry/exit zone is not violated first,
and protects an area in the event an intruder has hidden on the premises before the
system is armed, or gains access to the premises through an unprotected area.

Zone Characteristics:
• Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or

02) or interior-with-delay (type 10) zone is faulted first.

• Instant alarm in all other situations.

• Active when armed in AWAY or AWAY NO DELAY mode.

• Bypassed automatically when armed in STAY or STAY NO DELAY mode.

Type 05

Trouble by Day/

Alarm by Night

Zone type 05 is usually assigned to a zone that contains foil-protected doors or
windows or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also
be used on a sensor or contact in an area where immediate notification of an entry is
desired.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO

DELAY (night) mode.

• Provides a latched trouble sounding from the keypad and, if desired, a central

station report during the disarmed state (day).

Type 06
24-hour

Silent Alarm

Zone type 06 is usually assigned to a zone containing an Emergency
button (silent emergency).
Zone Characteristics:
• Sends a report to the central station but provides no keypad display or

sounding.

Type 01

Entry/Exit Burglary #1

01000-017-V0

Zone type 01 is usually assigned to sensors or contacts on primary entry and exit
doors.

Zone Characteristics:
• Entry delay #1 is programmable from 0-99 seconds (field

35).

• Exit delay is independently programmable from 0-99 seconds (field

34).

• Exit and entry delays when armed in AWAY or STAY mode.

• No entry delay when armed in STAY NO DELAY or AWAY NO DELAY mode.

• Exit delay regardless of the arming mode selected.