4-2. TROUBLESHOOTING
(Continued)

Display

Cause

Correction

AL-5

Temperature too low
in the hold mode.

Faulty control board - replace control board.
Faulty contactor - replace contactor.

AL-6

Temperature too high in
the hold mode.

Faulty control board - Replace board.
Door opened too much - Make sure door stays
closed as much as possible.

Problem

Cause

Correction

The evaporator is iced-up

Faulty De-icing Heater

Replace De-icing Heater

after a de-icing cycle.

Evaporator temperature at end

Increase the setting of step 8

of de-icing cycle too low.

in Section 3.

Maximum time of de-icing cycle

Increase the setting of step 7

too short.

in Section 3.

Too much water on evaporator

The unit has been shut down without

Start a de-icing cycle.

fins.

a de-icing cycle.

Slow to decrease

Compressor not working properly

Check compressor and re-

in temperature (decline in

place if neccessary.

performance)

Evaporator fan not working properly

Check the fan and replace if
neccessary.

Temperature of room too high.

Ventilate the room.

Not enough clearance around unit.

Change the location of the
unit. (See section 2-4)