Henny Penny BCC/BCR-140 User Manual

Page 27

Advertising
background image

Henny Penny

Model BCC/BCR-140, BCC/BCR-175, BFR/BCR-350

4-2. TROUBLESHOOTING
(Continued)

Problem

Cause

Correction

Slow to decrease

Condenser obstructed by dirt.

Clean the Condenser.

in temperature (decline in
performance)

Evaporator iced up.

Perform a de-icing cycle.

Refrigerating problem

Check refrigeration circuit and
components.

Display temperature does

In Frigiprobe mode, the display

Normal

not match the actual inlet air

shows the product temperature.

temperature. (No alarm)

In timer mode, or hold mode,

Ohm out the probe and check

the probe may be showing the

the reading with the table on

wrong temperature.

page 4-5. Change the probe if
it is out of tolerance.

Green compressor indicator

Compressor and condenser fan

light on and the compressor

do not work:

not working, or working

- Faulty contactor

Check contactor and change if

sometimes.

neccessary.

- Faulty control board relay-no

Replace control board.

voltage across terminals 10-11.

Compressor works, but condenser
fan does not:
- Faulty condenser fan

Replace fan.

Compressor and condenser fan
work together:
- Faulty protection component

Check items and replace if

for the compressor (overload

neccessary.

protector, potential relay, start
and run capacitor)

- Faulty overload protector of

Check fan and replace if

condenser fan.

necessary.

4-3

100

Advertising