After the fryer has been positioned under the exhaust hood, ensure the following has been
accomplished:

1. Adequate means must be provided to limit the movement of fryers without depending upon the

gas line connections. If a flexible gas hose is used, a restraining cable must be connected at all
times when the fryer is in use. The restraining cable and installation instructions are packed with
the flexible hose in the accessories box that was shipped with your unit.

DANGER

Do not attach an apron drainboard to a single fryer. The fryer may become unstable,
tip over, and cause injury. The appliance area must be kept free and clear of
combustible material at all times.

2. Level fryers equipped with legs by screwing out the legs approximately 1 inch then adjusting

them so that the fryer is level and at the proper height in the exhaust hood. Frymaster
recommends that the minimum distance from the flue outlet to the bottom edge of the hood be 24
in. (600 mm) when the appliance consumes more than 120,000 BTU per hour. NOTE: There
are no built-in leveling devices on fryers equipped with casters. The floor where the fryer is to
be installed must be level.


3. Test the fryer electrical system:

a. Plug the fryer electrical cord(s) into a grounded electrical receptacle.

b. Place the power switch in the ON position. Verify that the display indicates

CYCL.


c. Place the fryer power switch in the OFF position. Verify that the display indicates

OFF.


4. Refer to the data plate on the inside of the fryer door to determine if the fryer burner is configured

for the proper type of gas before connecting the fryer quick-disconnect device or piping from the
gas supply line.


5. Verify the minimum and maximum gas supply pressures for the type of gas to be used in

accordance with the accompanying tables.

Orifice Diameter

Single

Vat

Dual

Vat

Single

Vat

Dual

Vat

G20

20

2 x 3.40 2 x 3.40

7 mbar

7 mbar

G25

20 or 25

2 x 3.40 2 x 3.40

10 mbar

10 mbar

G30

28/30 or 50

2 x 2.05 2 x 2.05

17 mbar

17 mbar

G31

37 or 50

2 x 2.05 2 x 2.05

20 mbar

20 mbar

CE Standard

for Incoming Gas Pressures

for Fryers Manufactured After April 1999

(1) mbar = 10,2 mm H

2

O

Gas

Pressure

(mbar)

(1)

Regulator Pressure

Non-CE Standard

for Incoming Gas Pressures

Gas

Minimum

Maximum

Natural

6" W.C.

1.49 kPa

14.93 mbar

14" W.C.
3.48 kPa

34.84 mbar

LP

11" W.C.
2.74 kPa

27.37 mbar

14" W.C.
3.48 kPa

34.84 mbar

6. For fryers equipped with a FootPrint Pro system or basket lifts, plug the electrical cord(s) into a