6.8.1 Troubleshooting the Gas Valve

MAIN GAS SUPPLY

VALVE VERIFIED TO BE
OPEN AND EQUIPMENT

GAS VALVE IN ON

POSITION.

Is 24VAC

present on the main

coil (PV terminal) of

the gas valve?

Problem is with

the 24VAC circuit. Refer to

Troubleshooting the

24VAC Circuit.

What gas is the unit

configured for?

LP

(Propane)

Natural

Is incoming

gas pressure 6-14"

W.C. (1.49-3.49

kPa)?

Is incoming

gas pressure 11-14"

W.C. (2.74-3.49

kPa)?

Problem is with gas

supply to fryer.

Is burner manifold

gas pressure 3.5" W.C.

(0.8 kPa)?

Is burner manifold

gas pressure 8.25" W.C.

(2.5 kPa)?

Adjust pressure to

specification. If gas valve

will not adjust, replace

valve.

Is gas valve vent
tube obstructed?

Is gas valve vent
tube obstructed?

Clear obstruction.

Problem is not

with gas valve.

No

Yes

No

No

No

No

Yes

Yes

No

No

Yes

Yes

Yes

Yes