VeNtING INstAllAtIoN

Continued

It is not recommended that this appliance be

common vented with an existing gas burning

appliance. However, if it becomes necessary

to common vent this appliance, the venting

system must be sized and configured in ac-

cordance with the common venting guides

Appendix G of the current National Fuel Gas

Code NFPA No. 54/ANSI Z223.1.
Note: Before connecting this appliance to an

existing vent system or a common venting

system consult with your local architect, plan-

ner, or building official.

WARNING: This appliance

must be properly connected

to a system and must not be

connected to a chimney flue

servicing a separate solid fuel

burning appliance.

CHECKING FOR PROPER VENTING

After completing and checking electrical,

gas and vent connections, follow lighting

instructions and allow main burner to run

for approximately 5 minutes. Hold a lighted

match or cigarette near top edge of fireplace

opening and play it along entire length of

the opening (see Figure 12). Proper venting

should tend to draw the flame or smoke into

the appliance. Improper venting or escaping

of spillage of burned gas, is indicated when

the match flickers or goes out. Smoke from a

cigarette will also tend to disperse away from

the appliance.
If the appliance is found to be improperly

venting, shut it off and notify your installer

or a qualified service agency to inspect the

venting system.

NOTICE: This appliance is

equipped with a vent safety

shutoff switch which will shut

down the appliance in the case

of a venting problem. Do not

bypass the vent safety switch. If

the appliance should shut down,

contact a qualified installer, ser-

vice agency or your gas supplier

to have the vent inspected before

operating.

Lowest

Discharge

Opening

Listed

Vent Cap

8 Ft. Min.

Roof Pitch x/12

Listed Clearance

12

x

Listed

Gas

Vent

H (Min)

Height

From Roof

Roof Pitch

H (Min.) Ft.

m

Flat to 6/12

1.0

0.30

6/12 to 7/12

1.25

0.38

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2.0

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4.0

1.22

Over 12/12 to 14/12

5.0

1.52

Over 14/12 to 16/12

6.0

1.83

Over 16/12 to 18/12

7.0

2.13

Over 18/12 to 20/12

7.5

2.27

Over 20/12 to 21/12

8.0

2.44

Figure 10 - B-Vent Terminations

Check this area

along entire top

edge of fireplace

opening. Smoke

or flame should

be drawn into

appliance opening.

Figure 11 - Checking for Spillage