GAS LINE HOOK-UP

WARNING: Gas line hookup

should be done by your gas suppli-

er or a qualified service person.

WARNING: Before you pro-

ceed, make sure your gas supply

is OFF.

The appliance and it’s individual shutoff valve

must be disconnected from the gas supply

piping system during any pressure testing of

that system at test pressures in excess of 1/2

psig (3.5 kPa).
The appliance must be isolated from the gas

supply piping system by closing its individual

equipment shutoff valve during any pressure

testing of gas supply piping system at test pres-

sures equal to or less than 1/2 psig (3.5 kPa).
An equipment shutoff valve has been included

in the appliance’s gas supply system. You may

consider installing an extra gas shutoff valve

outside the appliance’s enclosure (check with

local codes) where it can be accessed more

conveniently with a key through a wall as

shown in Figure 15.
In conformance with local codes, route a

1/2" NPT gas line towards the appliance

coming in from any of the 3 directions shown

in Figure 16.

CAUTION: Do not kink flex-

ible gas line.

FMI PRODUCTS, LLC recommends that a

black iron gas line be routed from the gas

source, through a sediment trap (shown in

Figure 17, page 13) and into appliance. Once

connected through appliance, a flexible gas

line may be used for ease of installation to gas

control valve (see Figure 18, page 13).
Before connecting black iron gas line to inside

of appliance a sediment trap must be included

outside appliance between gas line and gas

shutoff valve. It must extend down 3" beyond

center of pipe. Prepare incoming black iron

gas line with teflon tape or pipe joint com-

pound (Check with local building codes).

FIrePlACe INstAllAtIoN

Continued

CAUTION: Compounds used

on threaded joints of gas piping

shall be resistant to the action

of Liquefied Petroleum (LP or

propane) and should be applied

lightly to ensure excess sealant

does not enter the gas line.

WARNING: All gas piping

and connections must be tested

for leaks after the installation is

completed.

After ensuring that the gas valve

is on, apply a commercial leak

detection solution to all con-

nections and joints. If bubbles

appear, leaks can be detected

and corrected.

Do not use an open flame for leak

testing and do not operate any

appliance if a leak is detected.

Complete your gas installation by connect-

ing incoming gas line with flexible gas line.

Secure tightly with wrench but

DO NOT

OVERTIGHTEN.

Figure 15 - Shutoff Valve Installation

Typical Exterior Wall Gas

Shutoff Installation

Key

Extension

Shutoff

Valve

Figure 16 - Routing Incoming Gas Line

8

3

/

8

"

10

5

/

8

"

1/2" NPT Incoming
Black Iron Gas Line

Flexible
Gas Line
(1 Provided)
Can Be
Extended Out
Either Side

7"

7"

Alternate Gas Supply
Through Sub-Floor

Advertising