Introduction, Selecting location – FMI PFS P324E User Manual

Page 5

Advertising
background image

www.fmiproducts.com

108794-01G

5

WARNING: Installation of

this appliance should be done

by a qualified service person

well trained in the installation

of such appliances. You will

also need a building permit from

your local Building and Safety

Commissioner before installing

this appliance; otherwise your

insurance company may not

cover this appliance.

NOTICE: This appliance is not

intended to be used as a primary

source of heat.

INtroduCtIoN

Continued

Figure 1 - Possible Locations for

Installing Appliance

INTERNAL WALL
INSTALLATION

CORNER
INSTALLATION

FULL
PROJECTION
INSTALLATION

FLUSH
INSTALLATION

To determine the safest and most efficient

location for your appliance, you must take into

consideration the following guidelines:
1. The location must allow for proper clear-

ances (see Clearances, page 7).

2. Consider a location where heat output

would not be affected by drafts, air con-

ditioning ducts, windows or doors.

3. A location that avoids the cutting of joists

or roof rafters will make installation easier.

Figure 1 shows a plan view of a few com-

mon locations.

Flush installations are recommended where

living space is limited or at a premium and

since the space required to enclose the ap-

pliance would be located beyond an outside

wall, this would also reduce the cutting of

joists, roof rafters and such. Check local

codes for any restrictions.
Projected installations can extend any

distance into the room. A projection may

be ideal for a new addition on an existing,

finished wall.

CAUTION: Do not connect

appliance before pressure test-

ing gas piping. Damage to gas

valve may result and an unsafe

condition may be caused.

The appliance and it’s individual shutoff valve

must be disconnected from the gas supply

piping system during any pressure testing of

that system at test pressures in excess of 1/2

psig (3.5 kPa).
The appliance must be isolated from the gas

supply piping system by closing its individual

manual shutoff valve during any pressure

testing of the gas supply piping system at

test pressures equal to or less than 1/2 psig

(3.5 kPa).
For the purpose of input adjustment two

pressure taps (for IN and OUT pressures)

are provided on the gas control valve for test

gauge connections to the appliance.

seleCtING loCAtIoN

Corner installations make use of space

that may not normally be used and provides

a wider and more efficient range for radiant

heat transference.
Internal wall installations provide a discreet

option for room separation and can also be

ideal as an addition to an existing wall.

Advertising
This manual is related to the following products: