Troubleshooting – FMI PFS P324E User Manual

Page 22

Advertising
background image

www.fmiproducts.com

108794-01G

22

trouBlesHootING

Note: Before troubleshooting the system, make sure the gas shutoff valve is ON. The two

most common causes of a malfunctioning gas appliance are:
1. Loose wiring connections
2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

Ignitor will not spark or pilot

will not light

Pilot will not stay lit

POSSIBLE CAUSE

1. No gas supply, or shutoff

valve is OFF

2. Air in gas line

3. Construction debris clog-

ging pilot orifice

4. Low gas pressure

5. Kinked pilot line

6. Control valve knob is not

opening

7. No power to unit or the

ignition module or power

transformer is bad

8. Vent damper not fully

open

1. Loose wiring on thermopile

to regulator valve. No mil-

livolt current is being sent

back to regulator

2. If valve knob and wall

switch are in the ON posi-

tion, probable defective

regulator valve

3. Vent damper not fully

open

REMEDY

1. Check to see if you have

gas supply and that equip-

ment shutoff valve is

opened

2. Repeat lighting procedure

several times to purge all

air out of lines. If after re-

peated attempts appliance

does not light, call for quali-

fied service and repair.

3. Remove debris and dirt,

inspect and clean any other

possible obstructions

4. Contact your gas supplier

to check pressure

5. Have a qualified technician

replace pilot line

6. Replace control valve (Re-

fer to Replacement Parts,

page 20)

7. Check that main power is

on and that all wire connec-

tions are made correctly to

ignition model (see Wiring

Diagram, page 21). Check

for 24 VAC at secondary

side of transformer. If 24

VAC is present, and mod-

ule does not operate, have

module replaced, otherwise

have transformer replaced

8. Open vent damper until

fully locked in the OPEN

position

1. Check wiring connections.

Refer to wiring diagram

shown in Wall Switch In-

stallation, page 11

2. Have a qualified technician

replace valve

3. Open vent damper until

fully locked in the OPEN

position