Installing and Maintaining the E1200i System

21

Each E1200i system requires at least two AC Power Supplies or at least one DC Power Supply to operate.

Three AC units are required for power supply redundancy, four AC units are required for full facility
redundancy, and six AC units provide 3+3 redundancy

Two DC units are required for power supply and full facility redundancy.

Refer to

Appendix D, on page 91

for specifications on thermal output and other power related numbers.

Fans and Airflow

Your E1200i chassis contains two field-replaceable fan trays. Air flows through the system from a
filtered-intake vent located in the lower part of the chassis. Air circulates from the bottom front (and sides)
to the back and exhausts through a top rear vent. The variable fan speed is reduced at normal operating
temperatures and increases to full speed as operating temperatures increase, up to 104° F (40° C).

For fan tray access, maintenance and proper ventilation, position the chassis and equipment rack or cabinet
so that:

At least three inches clearance is around the front and side intake and exhaust vents for free air flow

Provide 20 inches in the rear to access the fan tray.

Operate the E1200i system with two fan trays.

For instructions on replacing a fan tray, refer to

Removing and Replacing Fan Trays on page 65

.

Danger:

Make your chassis ground connections first (see

Figure 2

). If the chassis is not correctly

grounded, excessive electromagnet emission may result.

Disconnect all power to the equipment rack or cabinet before chassis installation.

Never operate the E1200i system with empty RPM, SFM, or line card slots. Always replace
empty slots with blank panels.

Danger: Leakage Current (High Touch Current): The AC power cords are secured to the power
inlet using the provided bracket. The AC power cord plugs must be secured to the building outlets
by the chassis installer or a qualified electrician.

Advertising