Installing and Maintaining the E1200i System

51

Figure 21 24 Port 1GE and 2-Port 10GE Line Card Port Numbering

Blank Panels

Blank panels for RPMs, SFMs, and line cards must be installed in empty slots to control airflow. If a slot is
not filled for more than five minutes, the following message appears on the console:

%CHMGR-2-MINORTEMP: Minor alarm: chassis temperature high (SFM

temperature reaches or exceeds threshold of 65C)

Blank panels are shipped with the system to ensure that all chassis slots are installed with operational
modules or blanks.

Preparing and Installing RPMs and Line Cards

To prolong the life of the EMI seals, begin installing cards in the right-most slot (slot 13), filling the slots
leftward (slot 12, then slot 11, then slot 10, and so on).

Caution: To avoid a chassis over-temperature condition, install blanks for RPMs, SFMs, and line card slots
not in use. Always replace cards or blanks immediately.