Installing and Maintaining the E1200i System

29

Figure 8 Rack-Mounting the Chassis

To install the chassis into a prepared rack:

Installing the Chassis into an Equipment Cabinet

Install the E1200i DC system after you secure the rack shelf bar. Load the chassis in the lower half of the
cabinet to avoid it becoming top-heavy. Make sure the cabinet is positioned with adequate space in the
front, rear, and sides of the unit for proper ventilation, access to cables, and access for maintenance.

Refer to

Chapter 3, Site Preparation

for complete requirements.

To install the chassis into an equipment cabinet:

Step

Task

1.

If you center- or rear-mount the chassis in a 19-inch rack, adjust the chassis rack-mounting brackets to
the desired position.

2.

If you mount the chassis in a 23-inch rack, install the 23-inch adapter brackets.

3.

Use a hand cart, pallet jack, or forklift to align the rack-mount holes with the equipment rack holes,
situating the chassis on top of the equipment rack shelf bar.

4.

Insert rack-mounting screws in the holes that are not obscured by the metal chassis shipping cover.
Tighten the screws. See

Figure 8

.

5.

Loosen and remove the screws that secure the chassis Front Shipping Cover and remove the cover.

6.

Insert the remaining rack-mounting screws and tighten to secure the chassis in the rack.

Step

Task

1.

Install the equipment rack shelf bar.

FN00046B