CHAPTER 6: PROGRAMMING OVERVIEW

38

EPM 5000 series Advanced Power Meters GE Multilin

6.3: Programming Mode Data Entry


The EPM 5300P and EPM 5200P programming mode utilizes only three out of the five-keypad buttons:
the MAX/MIN/LIMITS, VOLTS/THD, and AMPS/THD buttons.

THD

THD

MAX/MIN

LIMITS

VOLTS

AMPS

POWER

PHASE

NEXT

U

SED FOR

P

ROGRAMMING

U

SED FOR

P

ASSWORD

E

NTRY


Note: The EPM 5200P uses the same keypad strokes and methods. Although the keypad may look
slightly different, the keys match the EPM 5300P exactly. In the interest of brevity, all keystrokes and
programming functions are shown using the EPM 5300P keyboard.

BUTTON FUNCTION

DESCRIPTION

MAX/MIN/LIMITS ADVANCES

Scrolls GROUPS, FUNCTIONS and advances to exit point from
FUNCTION and GROUP level.

VOLTS/THD CHANGES

VALUE

Scrolls PACKS, digit counters and changes switch PACK position UP or
DOWN.

AMPS/THD

STORES

Activates new data entry and enters or exits from GROUP or FUNCTION
level.


6.4: Standard Numeric Data Entry


Programmable FUNCTION values are always four digit numerical fields designed to accept any value
between 0000 and 9999 (a blank signifies a zero). When entering the value of a FUNCTION, enter all
four digits, leading zeros included. For instance, to enter the number 25, enter 0025.