Programming steps – GE EPM 5200 User Manual

Page 55

Advertising
background image

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

GE Multilin EPM 5000 series Advanced Power Meters

51

PROGRAMMING STEPS:

1. Enter in GROUP 0, FUNCTION 4, PACK ‘P’, Segment C and D: UP, UP.
2. Enter in GROUP 5, FUNCTION 4, LIMIT 1, Segments B, C, and D: DOWN, UP, DOWN. Value: 58.00.
3. Enter in GROUP 5, FUNCTION 4, LIMIT 2, Segments B, C, and D: UP, UP, DOWN. Value: 62.00.

Example 2:
Normally reset—non-event condition is reset relay

Relay 1 will be “SET” if the instantaneous reading for amps is below 4.00 or above 5.00 amps. Under all
other conditions the relay will be “RESET”.

NOTE: Under this setup the relay will NOT act as a protective switch.


4 . 0 0 A

5 . 0 0 A

0 . 0 0 A

S E T

S E T

L M 2

L M 1

R E S E T

N O P O W E R T O T H E U N I T

R E S E T



PROGRAMMING STEPS:

1. Enter in GROUP 0, FUNCTION 4, PACK ‘p’, Segments C and D: DOWN, DOWN
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments: B, C, and D: UP, UP, DOWN. Value: 5.00
3. Enter in GROUP 4, FUNCTION 2, LIMIT 2, Segments: DOWN, UP, DOWN. Value: 4.00

GROUP 0—FUNCTION NUMBER DESCRIPTION

04.P

Controls Relay 1

05.P

Controls Relay 2 (and 3 if NL4)

Relay Mode: Group 0, Functions 4–5