CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

58

EPM 5000 series Advanced Power Meters GE Multilin

9.10: Group 0, Function 7—Number of Phases


NOTE:
E

NTER

1

FOR SINGLE PHASE

/

SINGLE WIRE

.

E

NTER

2

FOR SINGLE PHASE

/

TWO WIRE

.

E

NTER

3

FOR THREE PHASE

/

THREE OR FOUR WIRE

.

*STANDARD FACTORY SET-UP IS THREE-PHASE FOUR-WIRE


Note
: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

Step 1:

a. Enter Group Level of

Programming Mode. (Chapter 8)

b. Press MAX/MIN/LIMITS if 0.

does not appear.

c. Press AMPS to activate the

Group.

Step 2:
!

00. appears in upper display.

a. Press MAX/MIN/LIMITS until

07 appears in upper display.

b. Press AMPS to activate the

Group.

Step 3:

a. Press VOLTS to select numbers

1, 2 or 3.

b. Press AMPS to store.

See Chapter 14 to Exit.