CHAPTER 1: AC POWER MEASUREMENT

GE Multilin EPM 5000 series Advanced Power Meters

3


Voltages between the phases vary depending on loading factors and the quality of distribution
transformers. The three-phase system is distributed in different voltage levels: 208V AC, 480V AC, 2400V
AC, 4160V AC, 6900V AC, 13800V AC, and so on.

Power measurement in a poly phase system is governed by Blondel's Theorem. Blondel’s Theorem
states that in a power distribution network which has N conductors, the number of measurement elements
required to determine power is N-1. A typical configuration of poly phase system has either a Delta
connection or a Wye connection (see Figure 1.4, below).





N

A

B

C

2) Wye

X

E I

CN C

X

X

P = E I + E I + E I

AN

BN

CN

E I

BN B

E I

AN A

B

A

C

1) Delta

X

X

E I

CB C

E I

AB A

P = E I

AB A

+ E I

CB C

A

B

C

Figure 1.4: Poly Phase System: (1) Delta, (2) Wye






1.3: Consumption, Demand and Poor Power Factor


CONSUMPTION:

T

W

=

WH

×

W = instantaneous power T = time in hours

The total electric energy usage over a time period is the consumption of WH.

Typically, the unit in which consumption is specified is the kilowatt-hour (KWH): one thousand watts
consumed over one hour. Utilities use the WH equation to determine the overall consumption in a billing
period.

DEMAND
: Average energy consumed over a specified time interval. The utility determines the interval,
typically 15 or 30 minutes. The utility measures the maximum demand over a billing period. This
measurement exhibits a deviation from average consumption, causing the utility to provide generating
capacity to satisfy a high maximum consumption demand. The highest average demand is retained in the
metering system until the demand level is reset.


POOR POWER FACTOR
: Results in reactive power consumption. Transferring reactive power over a
distribution network causes energy loss. To force consumers to correct their Power Factor, utilities
monitor reactive power consumption and penalize the user for Poor Power Factor.