Group 1: voltage, amp, and watt scale settings, Description, Function 0: full scale voltage settings – GE EPM 5200 User Manual

Page 63

Advertising
background image

CHAPTER 10: PROGRAMMING GROUP 1

GE Multilin EPM 5000 series Advanced Power Meters

59


CHAPTER 10
PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE
SETTINGS

NOTE: The EPM 5300P and 5200P full scales will already be programmed if the order specified current
and voltage transformer ratios. The meter label indicates any full scale setup.

Programming Group 1 contains voltage, amperage and full scale power selection, along with scale factor
selection and decimal point placement.

The user can re-scale without removing the EPM 5300P for calibration. The 5300P has been calibrated at
standard levels in GROUP 2. Mathematically convert any full scale ratios to those calibrated levels. If a
different current or voltage transformer is used, program the primary value of its ratio. If necessary,
convert the ratio to a secondary value of five amps standard current (1 amp is a special order) and 120V
or 75V nominal voltage (options L only).



FORMULAS:

V

x 120

Secondary

Primary

75V

x

Secondary

Primary

5A

x

Secondary

Primary




It may be necessary to convert the full scale to a larger unit. There is a resolution limitation for all full
scales of 2000. If a display reading exceeds 2000, it may be unstable and subject to zeroing problems.

Example: The full scale for a CT ratio of 3000/5 should be 03.00 kA.

When changing a PT or CT full scale, calculate the new watts full scale and make any necessary
changes. The watts full scale will not auto range.

10.1: Group 1, Function 0—Full Scale Voltage Settings, Scale & Decimal Point
Placement



GROUP AND FUNCTION NUMBER

FUNCTION

10.

Full Scale Selection for Volts

11.

Full Scale Selection for Amps

12.

Full Scale Selection for Watts

1E.

Exit Programming GROUP 1

Table 10-1: Group 1 Programming Format


NOTE:

Tables 10-2 and 10-3 contain Full Scale Settings for typical voltages and currents

(PT and CT arrangements).