CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS

74

EPM 5000 series Advanced Power Meters GE Multilin

THERE ARE 3 SWITCHES TO SET WITH LIMITS:

1) Switch 1: Sets the limit to trip either above or below the Limit Value.
2) Switch 2: Sets whether Relay 1 will trip when the condition occurs.
3) Switch 3: Sets whether Relay 2 will trip when the condition occurs.

After the switches are set, the limit value should be programmed (see table in section 12.4).


LM1
LED

LM2
LED

SWITCH 1

ABOVE/BELOW

SWITCH 2

RELAY 1

SWITCH 3

RELAY 2

VALUE

ON

OFF

Digit Up-trigger above value

Digit Down-trigger below

value

Digit Up-enabled

Digit Down-

disabled

Digit Up-enabled

Digit Down-

disabled

0-9999
0-9999

OFF

ON

Digit Up-trigger above value

Digit Down-trigger below

value

Digit Up-enabled

Digit Down-

disabled

Digit Up-enabled

Digit Down-

disabled

0-9999
0-9999

Table 12.5: Group 5: Functions 0–7


LM1

LM2

SWITCH 1

SWITCH 2

SWITCH 3

VALUE

ON

OFF

Digit Up

Digit Up

Digit Down

0120

OFF

ON

Digit Down

Digit Down

Digit Up

0090

Table 12.6: Group 5: Example for Function 0

Thus, if Kilowatts exceed 120 W, LM1 is triggered and Relay 1 is tripped.
If the Kilowatts fall below 90 W, LM2 is triggered and Relay 2 is tripped.

SPECIAL CASES

FREQUENCY: FUNCTION 4 contains a permanent decimal after the second digit. The highest and
lowest level limits that can be programmed are 99.99 and 00.00, respectively.

POWER FACTOR:
FUNCTIONS 3 and 6 contain a permanent decimal after the first digit. The highest
and lowest limits that can be programmed are 1.000 and 0.000, respectively.