CHAPTER 10: PROGRAMMING GROUP 1

60

EPM 5000 series Advanced Power Meters GE Multilin

SECONDARY PT VALUES

PT RATIO

FULL SCALE

75 V (Suffix 75) L-N MAX

120:1

9.00 KV

120/208 V

1:1 (Direct)

120.0

120/208 V

4:1

0480 V

120/208 V

120:1

014.4 KV

277/480 V (Suffix G)

1:1 (Direct)

0300 V

120/208V 600:1

072.0

KV

120/208 1150:1

138.0

KV

Table 10-2: TYPICAL Full Scale Settings for Volts

If PT is connected line to line, the full scale can be 14.40 KV. Full scale is 300 V L-N, not 277, because
the factory calibration is 300 V. Be sure the table is based on a meter regulation of 2000 A/D counts.
Thus, for best accuracy, all settings should be placed within that range.




VOLTAGE FULL SCALE:


To change the Full Scale Settings:

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.



MAX/MIN

LIMITS

KVAR

PF
KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

Step 1:

a. Enter Group Level of Programming Mode

(see Chp. 8).

b. Press MAX/MIN/LIMITS until 1. appears in upper

display.

Step 2:

a. Press AMPS to activate GROUP 1.


!

10. appears in upper display.

!

Middle display indicates Scale Factor Setting.


!

Lower display indicates Full Scale for voltage.



Advertising
This manual is related to the following products: