CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

GE Multilin EPM 5000 series Advanced Power Meters

57

HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION:

S

ITUATION

1: FSW=9999.

• Selection is Multiply by 2

• This means that every .5 unit WH =1 pulse.

• Unit=Kilo (see Group 1, Function 2)

• Result: For every 1 KWH increment on the

counter, the meter will output 2 pulses.

S

ITUATION

2: FSW=999.9

• Selection is Multiply by 2

• This means that every .05 unit WH=1 pulse.

• Unit=Kilo (see Group 1, Function 2)

• Result: For every 1 KWH increment on the

counter, the meter will output 20 pulses.

S

ITUATION

3: FSW=99.99

• Selection is Multiply by 20

• This means that every .0005 unit WH=1 pulse.

• Unit=Kilo (see Group 1, Function 2)

• Result: For every 1 KWH increment on the

counter, the meter will output 2,000 pulses.

S

ITUATION

4: FSW=9.999

• Selection is Multiply by 20

• Unit=Kilo (see Group 1, Function 2)

• This means that every .00005 WH=1 pulse.

• Result: For every 1 KWH increment on the

counter, the meter will output 20,000 pulses.

HOW TO USE THE KYZ PULSE VALUE TABLE FOR DIVISION:

S

ITUATION

1: FSW=9999.

• Selection is Divide by 10

• This means that every 10 unit WH=1 pulse.

• Unit=Kilo (see Group 1, Function 2)

• Result: For every 10 KWH increment on the

counter, the meter will output 1 pulse.

S

ITUATION

2: FSW=999.9

• Selection is Divide by 10

• This means that every 1 unit WH=1 pulse.

• Unit=Kilo (see Group 1, Function 2)

• Result: For every 1 KWH increment on the

counter, the meter will output 1 pulse.

S

ITUATION

3: FSW=99.99

• Selection is Divide by 20

• This means that every .2 unit WH=1 pulse.

• Unit=Kilo (see Group 1, Function 2)

• Result: For every 1 KWH increment on the

counter, the meter will output 5 pulses.

S

ITUATION

4: FSW=9.999

• Selection is Divide by 20

• Unit=Kilo (see Group 1, Function 2)

• This means that every .02 WH=1 pulse.

• Result: For every 1 KWH increment on the

counter, the meter will output 50 pulses.


To change the KYZ pulse value:

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

Step 1:

a. Enter Group Level of

Programming Mode, (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0.

appears in upper display.

c. Press AMPS to activate the

Group.

Step 2:

a. Press MAX/MIN/LIMITS until 06.P

appears in upper display.

!

The lower display indicates

multiplication or division factor.

Step 3:

a. Press AMPS to change current

setting.

!

The decimal point next to the 6

disappears.

b. Press MAX/MIN/LIMITS to

advance selections. -or-

c. Press VOLTS to reverse.

(Until desired factor appears).


!

Division is indicated by div

appearing in the middle display.

When middle display is blank, it

indicates multiplication.

d. Press AMPS to store.