CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

GE Industrial Systems 5300P Advanced Power Meter

43

CHAPTER 9
PROGRAMMING GROUP 0 – GLOBAL METER SETUP



The Global Meter Setup includes FUNCTIONS 0 through 7 that control configuration and basic operation.
FUNCTION 3 System Configuration contains Switch PACKS with various options, including Open Delta
installation, communications or DC Output setup. Global Meter Setup is the section in which general
features are programmed.

FUNCTION

NUMBER

Function

0. Integration

Interval

1.

Meter Address for Communication

2.

Baud Rate for Communication

3.

System Configuration (see Table 9-2)

4.

Relay 1 Set-up / Time delay

5.

Relay 2 Set-up / Time delay

6.

KYZ Parameter Selection

7.

Number of Phases

E.

Exit Programming GROUP 0

Table 9-1: Group 0 Programming Format


9.1: Group 0, Function 0—The Integration Interval


INTEGRATION INTERVAL:
Time which all instantaneous readings are averaged to obtain a max and
min demand. The Integration Interval is entered in seconds. When entering 15 minutes, enter: 0900
seconds. The default value is 900 seconds.

To change the Integration Interval:

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

Step 1:

a. Enter Group Level of Programming Mode

(see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears in upper

display.

c. Press AMPS to activate the Group.


!

Function 00. appears in upper display. The second 0

indicates Function 0


!

Lower display indicates current Interval setting.