Kyz pulse outputs, Standard rate table for watts, Kyz pulse outputs: nl2 option – GE EPM 5200 User Manual

Page 19

Advertising
background image

CHAPTER 3: ELECTRICAL INSTALLATION

GE Multilin EPM 5000 series Advanced Power Meters

15

20

21

22

23

24

25

26

27

28

N.O.

N.C.

COM

N.O.

N.C.

COM

K

Y

Z

ALAR M #1

ALAR M #2

PULSE
O U TPUT

Figure 3.1: Close-up of the Relay and KYZ pulse output on the rear panel.


Note: The relays shown in the figure above are in the NOT energized state.

THE INSTRUMENT DETECTS TWO LEVELS OF ALARM FOR THE FOLLOWING FUNCTIONS:
"

Voltage:

AN, BN, CN, AB, BC, CA

"

Current:

A, B, C, N

"

Over and Reverse Power

"

Under PF/KVAR Lead or Lag

"

Over

KVA

"

Voltage Imbalance (One level only)

"

Over/Under

Frequency

"

Voltage Phase Reversals (One level only)

"

Over/Under %THD (Available only with option –H)

"

Over/Under

K-Factor


KYZ RELAYS: Provides pulses for energy management systems or any other type of recording device.
These pulses represent accumulated watt-hour, negative watt-hour, or VA-hour. Accomplish this
assignment through the Programming Mode (see programming sections). The pulse value is determined
by the decimal increment of the power function assigned to the pulse. The EPM 5200P can be equipped
with KYZ pulse outputs.

NOTE: Unless otherwise specified, standard KYZ setup represents positive watt hour. See table below
for standard rate.
The scale factor for wattage (KW or MW) and Full Scale Decimal Point Placement is
selectable in Programming Mode GROUP 1, FUNCTION 2. Follow the Decimal Point Placement
corresponding to the Change in Level. A multiplication or division factor can be programmed. See
Programming GROUP 0, FUNCTION 6 for a different rate.

STANDARD RATE TABLE FOR WATTS*

DECIMAL POINT PLACEMENT

(KW/MW)

CHANGE IN LEVEL

9999.000 1.0

Units

W-Hour

999.900 0.1

Units

W-Hour

99.990

0.01 Units W-Hour

9.999 0.001

Units

W-Hour

*Units could be KiloWatts or MegaWatts.

3.8: KYZ Pulse Outputs: NL2 Option


The -NL2 option for the meter is equipped with three KYZ outputs. KYZ relays provide pulses for energy
management systems or any other type of recording device. These pulses represent accumulated
positive watt-hour, negative watt-hour, VA-hour, positive VAR-hour, or negative VAR-hour. Accomplish
this through Programming Mode GROUP 0, FUNCTION 6. The pulse value is dependent upon the
Decimal Point Placement and is determined by the decimal increment of the power function assigned to
the pulse. Refer to the situation that applies to the meter setting.