CHAPTER 10: PROGRAMMING GROUP 1

62

EPM 5000 series Advanced Power Meters GE Multilin

10.2: Group 1, Function 1—Amperage Full Scale



CT T

YPE

FULL

SCALE

Direct Input

05.00 A

600/5 0600

A

1000/5 1000

A

2000/5 2000

A

3000/5 03.00

KA

5000/5 05.00

KA

Table 10-3: Full Scale Settings for Amps




Also note that the meter reads with digital accuracy to a 2000 count range. Thus all CT and PT full scale
settings in the meter should reflect that limitation. The table above shows the proper settings.



To change the Full Scale Settings:



NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.


MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

MAX/MIN

LIMITS

KVAR

PF

KW
KVA

FREQ

KWH

KVAH

AC VOLTS

AC AMPS

POWER

N

C

B

A

MAX
MIN

A

N

B

N

C

N

A

B

B

C

C

A

LM2

LM1

NEXT

PHASE

VOLTS AMPS

POWER

Step 1:

a. Enter Group Level of Programming Mode

(see Chp. 8).

b. Press MAX/MIN/LIMITS until 1. appears in

upper display.

Step 2:

a. Press AMPS to activate the Group.

b. Press MAX/MIN/LIMITS until 11. appears in

upper display.

!

Middle display indicates Scale Factor Setting.


!

Lower display indicates Full Scale.