CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS

GE Multilin EPM 5000 series Advanced Power Meters

73

LM1 LED

LM2 LED

ABOVE/BELOW

RELAY 1

RELAY 2

VALUE

ON

OFF

Digit Up

Digit Up

Digit Down

0135

OFF

ON

Digit Down

Digit Down

Digit Up

0090

Table 12.3: Group 4: Example for Function 0


EXAMPLE

: If voltages exceed 135 V, LM1 is triggered and Relay 1 is enabled. If the voltages fall below

90 V, LM2 is triggered and Relay 2 is enabled.

12.4: Group 5, Functions 0–7—LM1/LM2 Set Limits

M A X / M IN

L I M I T S

K V A R

P F

K W

K V A

F R E Q

K W H

K V A H

A C V O L T S

A C A M P S

P O W E R

N

C

B

A

M A X

M I N

A

N

B

N

C

N

A

B

B

C

C

A

L M 2

L M 1

N E X T

P H A S E

V O L T S

A M P S

P O W E R

U S E V O L T S T O

T O G G L E B E T W E E N

L M 1 A N D L M 2 .

T H E L I M I T V A L U E

S I N C E T H I S I S G R O U P 5 , F U N C T I O N 0 ,

F R O M L E F T T O R I G H T : S E T L I M I T

A N D T R I P R E L A Y 2

T H E K W A N N U N C I A T O R

A B O V E / B E L O W , T R I P R E L A Y 1

G L O W S


GROUP 5 contains LM1 and LM2 set limit values for all power functions. This allows the user to program
limits for the following functions: Kilowatt, Kilovar, Kilovolt-ampere, Power Factor, Frequency, negative
Kilovar, negative Power Factor, and negative Kilowatt.


GROUP AND FUNCTION NUMBER

FUNCTION

50.

LM1/LM2 Set Limits for Kilowatt

51.

LM1/LM2 Set Limits for Kilovar

52.

LM1/LM2 Set Limits for Kilovolt-ampere

53.

LM1/LM2 Set Limits for Power Factor

54.

LM1/LM2 Set Limits for Frequency

55.

LM1/LM2 Set Limits for Negative Kilovar

56.

LM1/LM2 Set Limits Negative Power Factor

57.

LM1/LM2 Set Limits for Negative Kilowatt

5E.

Exit Programming GROUP 5

Table 12.4: Group 5 Programming Format for Limit Condition