Hre water supply connection location – Greenheck Fan HEAT RECOVERY UNIT WITH EVAPORATIVE COOLING HRE-20 User Manual

Page 11

Advertising
background image

11

7 . Verify that both airflow and system static pressure are in agreement with the specifications . If these

conditions are met, check for water carry over from the discharge side of the media . If carry over is
observed, check the distribution header for holes or tears and the water standoff tube for blockage .

8 . After all final adjustments are made, remove the jumper wires, connect “call for cooling” signal, and replace

all access panels . The unit is now ready for operation .

Bleed-Off

Valve

Overflow

Pump

Filter

Threaded

Float

Adjustment

Supply

Connection

Float

Valve

Pump and Float Components

HRE WATER SUPPLY CONNECTION LOCATION

B

A

Ø 0.875

Run 1/4 inch line up through 7/8 inch

hole here and bring around end

of sump to supply connection.

D

C

Ø 0.875
Run 1/4 inch line up through 7/8 inch
hole here and bring around end
of sump to supply connection.

OA INLET

EA INLET

1/4 inch Water Supply Connection

1/4 inch Water Supply Connection

Model

Water Supply Connection Locations

A

B

C

D

HRE-20

37 .375

4 .625

4 .625

39 .25

HRE-45

38 .75

4 .625

4 .625

43 .00

HRE-55

43 .50

4 .625

4 .625

46 .125

HRE-90

43 .50

4 .625

4 .625

52 .625

Dimensions from outside of unit (in inches)

Top View

Water Flow Adjustment Device

Advertising