Optional accessories, Factory setpoints – Greenheck Fan HEAT RECOVERY UNIT WITH EVAPORATIVE COOLING HRE-20 User Manual

Page 21

Advertising
background image

21

S1 to SN contact for On/Off
A1 (0-10VDC) referenced to AC (Can use +15 VDC from +V)

Parameter

Setting

A1-01

Access Level

2

C6-02

Carrier frequency

2

d2-02

Ref Lower Limit

50%

E2-01

Motor Rated FLA

Motor FLA

H3-03

Terminal A1 Bias

50%

O2-03

User Defaults

1

A1-01

Access Level

0

S1 to SC contact for On/Off
FR (0-10VDC) referenced to FC (Can use +12 VDC from FS)

Parameter

Setting

n01

Access Level

1

n31

Ref Lower Limit

50%

n32

Motor Rated FLA

Motor FLA

n40

Multi-Function output (MA,MB,MC)

0

n42

Analog Freq . Reference Bias

50%

n46

Carrier Frequency

2

n01

Access Level

0

Factory Setpoints -

MODULATING CONTROL (0-10 VDC) FOR FAN SPEED

Yaskawa E7 Drive

Yaskawa GPD-305 Drive

OPTIONAL ACCESSORIES

Variable frequency drives (VFD) for the blowers are factory setup to receive a 0-10 VDC signal wired in the field
(refer to previous page for terminal locations) . Most of the setpoints in the VFDs are factory defaults . There are
a few, though, that are changed at Greenheck and are shown in the tables below . To gain access to change
setpoints on the E7 drive, parameter A1-01 needs to be set at “2” . To gain access to change setpoints on the GPD-
305 drive, parameter n01 needs to be set at “1” . To prevent access on either drive, change the parameter to “0” .

Factory Setpoints -

MULTI-SPEED CONTROL (1/3 OR 1/2 SPEED REDUCTION) FOR FAN SPEED

S1 to SN contact for On/Off

Parameter

Setting

A1-01

Access Level

2

b1-01

(Frequency) Reference Source

0

C6-02

Carrier frequency

2

d1-01

Frequency Reference 1

60

d1-02

Frequency Reference 2

40

d1-03

Frequency Reference 3

30

d1-04

Frequency Reference 4

60

E2-01

Motor Rated FLA

Motor FLA

O2-03

User Defaults

1

A1-01

Access Level

0

Yaskawa E7 Drive

S1 to SC contact for On/Off

Parameter

Setting

n01

Access Level

1

n03

Reference Selection

1

n21

Frequency Reference 1

60Hz

n22

Frequency Reference 2

40Hz

n23

Frequency Reference 3

30Hz

n24

Frequency Reference 4

60Hz

n32

Motor Rated FLA

Motor FLA

n38*

Multi-function Input Sel 4 (Term S4)

6

n39*

Multi-function Input Sel 5 (Term S5)

7

n40

Multi-Function output (MA,MB,MC)

0

n46

Carrier Frequency

2

n01

Access Level

0

*Parameter n39 must be set to 7 before n38 can be set to 6 (the
drive does not allow these parameters to be the same number, n39
default is 6)

Yaskawa GPD-305 Drive

Variable Frequency Drives for
Energy Recovery Wheel

Factory installed VFD for the energy recovery wheel are programmed at the factory per the settings shown
below . Refer to the instruction manual that ships with the unit when making adjustments . A copy of the manual
can be found online at www .drives .com . For technical support, contact Yaskawa direct at 1-800-927-5292 .

Parameter

Setting

n01

Access Level

1

n30

Ref Upper Limit

100% or 66%*

n32

Motor Rated FLA

Motor FLA

n33

Elect Thermal Overload

1

n36

Multi-Function input (terminal S2)

10

n40

Multi-Function output (MA,MB,MC)

4

n41

Analog Freq . Reference Gain

0

n42

Analog Freq . Reference Bias

99

n46

Carrier Frequency

2

n58

Frequency Detection Level

20

n01

Access Level

0

Yaskawa GPD-305 Drive

*36 inch wheel is 66% (40Hz) . All other wheels are 100% (60Hz) .