*Always provide the unit model and serial number when requesting parts or service information. *Always check motor amps and compare to nameplate rating.

Energy Wheel

Does NOT Turn

Blower fan motor overloads are
tripping and auto-resetting .

Decrease fan speed .

Possible Cause

Symptom

Corrective Action

Exhaust Only frost control
sensors are tripping .

Adjust frost temperature sensor set point as needed .

Air seals are too tight .

See Energy Recovery Wheel under Unit Start-Up section .

‘Economizer’ sensors are
operating .

Adjust temperature or enthalpy set points as needed .

No power to wheel motor.

Make sure wheel drive is plugged in . Verify power is
available .

Wheel drive belt

Check for loose or broken belts . Replace belts (consult
factory) .

One or Both

Blowers Turn Off

Intermittently and

Back on After

About 2 Minutes

Wheel motor overloads are
tripping, due to rubbing
between wheel and air seals .

Recheck air seals, make sure they are not too tight . See
Energy Recovery Wheel under Unit Start-Up Section .

Fan wheel rubbing on inlet

Adjust wheel and/or inlet cone . Tighten wheel hub or bearing
collars on shaft .

Bearings .

Replace defective bearings (s) . Lubricate bearings . Tighten
collars and fasteners .

Wheel out of balance .

Replace or rebalance .

Loose wheel on shaft .

Tighten wheel setscrew .

Energy Wheel

Runs Intermittently

Loose motor or blower sheave .

Tighten sheave setscrew .

Belts too loose .

Adjust belt tension after 24 hours of operation .

Belts too tight .

Loosen to maintain a 3/8 inch deflection per foot of span
between sheaves .

Worn belt .

Replace .

Motor base or blower loose .

Tighten mounting bolts .

Build-up of material on wheel .

Clean wheel and housing .

Bearing and drive misaligned .

Realign .

Noise being transmitted by
duct .

Make sure duct work is supported properly . Make sure duct
work metal thickness is sized for proper stiffness . Check duct
size at discharge to ensure that air velocities are not too high .

Excessive Noise or

Vibration

Troubleshooting

#461248 IOM HRE FS

Rev . 4, April 2012

Copyright © 2012 Greenheck Fan Corp .

Warranty

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the purchase date . The energy recovery wheel is warranted to be free from defects in material and workmanship for a
period of five years from the purchase date . Any units or parts which prove defective during the warranty period will be
replaced at our option when returned to our factory, transportation prepaid .

Motors are warranted by the motor manufacturer for a period of one year . Should motors furnished by Greenheck prove
defective during this period, they should be returned to the nearest authorized motor service station . Greenheck will not
be responsible for any removal or installation costs .