Rooftop units require curbs to be mounted first . The duct connections must be located so they will be clear of
structural members of the building .

1. Factory Supplied Roof Curbs

Roof curbs are Model GKD, which are shipped in a
knockdown kit (includes duct adapter) and require field
assembly (by others) . Assembly instructions are included
with the curb .

2. Install Curb

Locate curb over roof opening and fasten in place . (Refer
to Recommended Roof Openings) . Check that the diagonal
dimensions are within ±1/8 inch of each other and adjust as
necessary . For proper coil drainage and unit operation, it is
important that the installation be level . Shim as required to
level .

3. Install Ductwork

Installation of all ducts should be done in accordance with
SMACNA and AMCA guidelines. Duct adapter provided to
support ducts prior to setting the unit .

4. Set the Unit

Lift unit to a point directly above the curb and duct
openings . Guide unit while lowering to align with duct
openings . Roof curbs fit inside the unit base . Make sure the
unit is properly seated on the curb and is level .

L

W

All dimensions shown are in inches .

Curb Outside Dimensions

Roof curb details, including duct location

dimensions, are available on HRE roof curb

assembly instructions.

ROOF CURB

SIDE OF UNIT

BASE

1 INCH INSULATION

E

D

C

A

B

Curb Outside Dimensions

Weight

Model

L

W

HRE-20

93

51

280

HRE-45

100 .5

60 .63

355

HRE-55

112 .75

71 .5

450

HRE-90

125 .75

90 .75

625

Model

Curb Cap Dimensions

A

B

C

D

E

HRE-20

2 .00

2 .00

1 .00

0 .88

0 .75

HRE-45

2 .00

4 .25

2 .00

1 .31

0 .50

HRE-55

2 .00

4 .25

2 .00

1 .31

0 .50

HRE-90

2 .00

4 .25

2 .00

1 .31

0 .50

All dimensions shown are in inches .

Curb CAP Details for Factory Supplied Roof Curbs

ROOF CURB MOUNTING