Routine maintenance, Energy recovery wheel maintenance – Greenheck Fan HEAT RECOVERY UNIT WITH EVAPORATIVE COOLING HRE-20 User Manual

Page 38

Advertising
background image

38

Access to wheel through

outdoor air filter door

The HRE units have one energy recovery wheel . Open the outdoor
air filter door to access the wheel . For the HRE-20 and HRE-45
models, the wheel cassette slides out . Due to the size and weight
of the HRE-55 and HRE-90 wheels, they remain stationary and all
maintenance is performed in place . There is room inside the unit to
perform energy recovery wheel servicing . Filters must be removed to
access stationary wheels .

**WARNING: Disconnect power to the unit before performing

any type of service.

ACCESSING ENERGY RECOVERY WHEEL

Energy Recovery Wheel Maintenance

Annual inspection of the energy recovery wheel is recommended . Units
ventilating smoking lounges and other non-clean air spaces should
have energy recovery wheel inspections more often based upon need .
Inspections for smoke ventilation applications are recommended
bimonthly to quarterly until a regular schedule can be established .

ROUTINE MAINTENANCE

IMPORTANT! PLACE RETAINERS BACK IN THE

ORIGINAL POSITION BEFORE
ROTATING THE ENERGY RECOVERY WHEEL.
OTHERWISE DAMAGE TO RETAINER WILL
OCCUR.

Bracket Segment Retainer

Lift Away

From Segment

Catch-

Segment Retainer

Push Toward Center

Center of Wheel

Spoke

Inside of Wheel Rim

Models HRE-20, 45, 55, & 90

Steel retainers are located on the
inside of the wheel rim (see diagram
at right) . Push the retainer toward
center of wheel, then lift up and
away to release segments (see
below) .

REMOVING THE ENERGY RECOVERY WHEEL SEGMENTS

Wheel segment removed

Advertising