Routine maintenance – Greenheck Fan HEAT RECOVERY UNIT WITH EVAPORATIVE COOLING HRE-20 User Manual

Page 37

Advertising
background image

37

External Filter Maintenance

Aluminum mesh, 2-inch deep filters are located in the
supply weatherhood (if the weatherhood option was
purchased) . Filters should be checked and cleaned on
a regular basis for best efficiency . The frequency of
cleaning depends upon the cleanliness of the incoming
air . These filters should be cleaned prior to start-up .

To access these filters, remove bottom bolt in the access
door on the side of the weatherhood . Slide the access
door up and then pull bottom out to remove door . Then,
slide the filters out (see figure at right) .

Clean filters by rinsing with a mild detergent in warm
water .

Internal Filter Maintenance

The HRE units will typically be provided with 2-inch,
pleated filters in the outdoor air and exhaust airstreams .
These filters should be checked per a routine
maintenance schedule and replaced as necessary to
ensure proper airflow through the unit . See table at
right for pleated filter size and quantity for each unit .
Replacement filters shall be of same performance and
quality as factory installed filters . Filter type must be
pleated design with integral metal grid . Two acceptable

filter replacements are Aerostar Series 400 or Farr 30/30

®

.

Outdoor Air Filters: Access to the outdoor air filters
is through the door labeled as “Filter Access” on the
outdoor air side of the unit .

Exhaust Air Filters: Access to the exhaust air filters
is through the door labeled as “Filter Access” on the
exhaust air side of the unit .

Refer to Access Door Descriptions section for additional
information on filter locations .

Door Seal Maintenance

Slip-on type vinyl seal is installed on the perimeter of the
door openings . Inspect at least annually to ensure that
seal is still pliable and intact .

Outdoor air intake hood

mesh filter access

ROUTINE MAINTENANCE

Filter Size and Quantities

Model

Internal

Filter Size

Quantity

Supply

Quantity

Exhaust

HRE-20

20 in . x 20 in .

2

2

HRE-45

20 in . x 25 in .

3

3

HRE-55

16 in . x 25 in .

6

6

HRE-90

20 in . x 20 in .

8

8

Bearings

Most bearings are permanently lubricated and require not further lubrication under normal use. Normal use
being considered -20ºF to 120ºF and in a relatively clean environment . Some bearings are re-lubricatable and
will need to be regreased depending on fan use . Check your bearings for grease zert to find out what type of
bearing you have . If your fan is not being operated under normal use, bearings should be checked monthly for
lubrication .