28

OPTIONAL ACCESSORIES

RAI

RAF-P

RA

FILTER

OAAW

COOL

COIL

ACC

HEAT

COIL

OAF-A

OAD

SUPPLY

BLOWER

TO INSIDE

FROM INSIDE

EW-P

OAW-P

ENERGY WHEEL

EAW

EF-A

OAI

OA

FILTER

OAF-P

TO

OUTSIDE

FROM

OUSTIDE

EXHAUST

BLOWER

Sensors Mounted by Factory

Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit
diagram below . A list of available sensors is shown below . The specific sensors provided on a given unit are
labeled in the unit control center on the terminal strip . Sensors are wired to the terminal strip to make it easy for
the controls contractor to connect the Building Management System for monitoring purposes .

Pressure Sensors (analog or digital)

Drawing Labels

Terminal Strip Labels

OAF-P

OA/Supply Filter Pressure

OAW-P

Outdoor Air Wheel Pressure

RAF-P

RA/Exhaust Filter Pressure

EW-P

Exhaust Wheel Pressure

Amp - Current Sensors (analog or digital)

Drawing Labels

Terminal Strip Labels

OAF-P

Supply Fan Amps

EF-A

Exhaust Fan Amps

Temperature Sensors - 1K Ohm RTD

Drawing Labels

Terminal Strip Labels

OAI

OA/Supply Inlet Temp

OAAW

OA After

ACC

After Cooling Coil Temp

OAD

Supply Discharge Temp

EAW

Exhaust After Wheel Temp

RAI

RA/Exhaust Inlet Temp