Optional accessories, Variable frequency drives for blowers – Greenheck Fan HEAT RECOVERY UNIT WITH EVAPORATIVE COOLING HRE-20 User Manual

Page 20

Advertising
background image

20

Variable Frequency Drives for Blowers

Optional factory installed, wired, and programmed variable frequency drives (VFD) may have been provided
for modulating or multi-speed control of the blowers . One VFD is provided for each blower (outdoor air and
exhaust) . The VFDs provided are either Yaskawa model E7 or model GPD305 . Refer to the tables on the
next page for factory settings and field wiring requirements . Refer to the unit control center for unit specific
wiring diagram (an example wiring diagram has been provided in this section for reference) . When making
adjustments outside of the factory setpoints, refer to Yaskawa VFD instruction manual, which can be found
online at www .drives .com . For technical support, contact Yaskawa direct at 1-800-927-5292 .

S3

SN SC SP

E(G)

S1 S2

MC

MB

MA

A1 A2 +V AC

AC

R+ R-

M4

S6

S5

S4

FM

S7

AC

S-

IG

AM

S+

M3

M2

M1

E(G)

DATA

ENTER

STOP

HAND

RUN

OFF

RESET

MENU

MONITOR

AUTO

ESC

YASKAWA E7

YASKAWA
GPD 305/J7

S2

MA MB MC

S1

FS

S3 S4

SC

S5

AM

FR FC

AC

STOP

RESET

DATA

ENTER

DSPL

RUN

MAX

MIN

FOUT

F/R

FREF

MNTR
PRGM

LO/RE

IOUT

OPTION 1 - 0-10 VDC CONTROL

FC

FR

0-10 VDC CONTROL SIGNAL (BY OTHERS)
WIRED TO FR (+) AND FC (COMMON)

OPTION 2 - MULTI SPEED CONTROL

S5

S4

SC

YASKAWA BLOWER VFD DETAIL WIRING

NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.

DRIVE SPEED = 40 Hz.

S4 TO SC CONTACT CLOSED (BY OTHERS)

S5 TO SC CONTACT CLOSED (BY OTHERS)

DRIVE SPEED = 30 Hz.

TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER n01 CHANGE TO 1

PARAMETER n22 FOR NEW 40Hz SETTING

PARAMETER n21 FOR NEW 60Hz SETTING

PARAMETER n23 FOR NEW 30Hz SETTING
PARAMETER n01 CHANGE TO 0

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS FS AND FR.

0 VDC=30 Hz

10 VDC=60 Hz

USER TO PROVIDE CONTACTS

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

OPTION 1 - 0-10 VDC CONTROL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

USER TO PROVIDE ISOLATION AS REQUIRED

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.

WIRED TO A1 (+) AND AC (COMMON)

0-10 VDC CONTROL SIGNAL (BY OTHERS)

10 VDC=60 Hz

0 VDC=30 Hz

A1 AC

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

PARAMETER A1-01 CHANGE TO 0

PARAMETER D1-03 FOR NEW 30Hz SETTING

PARAMETER D1-01 FOR NEW 60Hz SETTING
PARAMETER D1-02 FOR NEW 40Hz SETTING

PARAMETER A1-01 CHANGE TO 2

TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.

DRIVE SPEED = 30 Hz.

S6 TO SN CONTACT CLOSED (BY OTHERS)

S5 TO SN CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 40 Hz.

DRIVE SPEED = 60 Hz.

NEITHER S5 OR S6 CONTACT CLOSED

SN

S5 S6

USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED

OPTION 2 - MULTI SPEED CONTROL

AND ISOLATION AS REQUIRED

USER TO PROVIDE ISOLATION AS REQUIRED

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

Drawing No. 116329

Part No. 465535

OPTIONAL ACCESSORIES