Model PVe Heat Recovery Unit
Typical Control Center Components
 1. Main Disconnect (non-fusible, lockable)
 2. Motor Starter
 3. Motor Starter
 4. Power Distribution Blocks
 5. 24 VAC Control Transformer 
 6. 24 VAC Terminal Strip
 7. Temperature Sensor with Override (used for 
Economizer Mode)
 8. Dirty Filter Sensor
 9. Dirty Filter Sensor
Electric Heater Application/Operation
Factory installed electric heaters are optionally 
provided in order to provide preheat frost control. 
An electric preheater warms the outdoor air prior to 
being drawn through the PVe plate heat exchanger. 
Electric heaters are available in 208, 230, or 460 VAC. 
Refer to heater nameplate for voltage rating.
Preheaters: If an optional preheater is supplied with 
the unit, it is installed as a single stage on/off control. 
Preheaters are single-point wired at the factory. A 
thermocouple type 
temperature sensor 
is mounted in the 
outdoor airstream 
after the preheater and 
that thermocouple will 
switch the preheater 
on. See Frost Control 
Application/Operation 
for typical set points. 
If the temperature falls 
below the set point 
and a pressure drop 
sensor is triggered, the 
preheater will turn on.