Roof curb and rail mounting, Service clearances duct dimensions, Intake and discharge options – Greenheck Fan PVE-35 User Manual
Page 5: Bc a d d
 
5
Model PVe Heat Recovery Unit
When installed on a roof, a typical installation 
will include at least one roof penetration in order 
to deliver return air to the unit from the space. 
Additionally, a second roof penetration may be used 
for supply air discharge to the space.
Roof Curb and Rail Mounting
Service Clearances
Duct Dimensions
Position the unit roof opening such that the Return Air 
Intake will line up with the corresponding ductwork. 
If applicable, adjust position to also accommodate 
the SA Discharge vent. Make certain that proposed 
positioning of the unit still maintains recommended 
service clearances.
Option
Bottom
Top
Side
End
OA Intake
X
SA Discharge
X
X
RA Intake
X
EA Discharge
X
OA - Outdoor Air
SA - Supply Air (to the space)
RA - Return Air (from the space)
EA - Exhaust Air
Model
A
B
C
D
E
F
PVe-20
10.7
(280)
12.2
(310)
10.3
(270)
11.8
(300)
22.0
(570)
14.0
(360)
PVe-35
11.9
(310)
13.7
(350)
11.4
(290)
13.1
(340)
34.0
(870)
14.0
(360)
PVe-45
14.1
(360)
16.0
(410)
13.3
(340)
14.5
(370)
46.0
(1170)
14.0
(360)
PVe-55
16.4
(420)
19.2
(490)
15.9
(450)
18.6
(480)
60.0
(1530)
14.0
(360)
All dimensions are shown in inches (millimeters).
Intake and Discharge Options
Bypass
Damper
Face
Damper
Outdoor Air Hood
Filters
Filters
Filters
Exhaust
Air Hood
Control Center
Face/Bypass Damper
Plate Heat
Exchanger
Plate Heat
Exchanger
Outdoor
Air Hood
C
B
A
D
E
CLEARANCE
CLEARANCE
B
C
A
D
D
OA Intake
RA Intake
SA Discharge
EA Discharge
B
A
C
D
E
F
Model
A
B
C
D
PVe-20
36
(920)
36
(920)
36
(920)
60
(1530)
PVe-35
48
(1220)
36
(920)
36
(920)
60
(1530)
PVe-45
60
(1530)
36
(920)
36
(920)
60
(1530)
PVe-55
72
(1830)
36
(920)
36
(920)
60
(1530)
All dimensions are shown in inches (millimeters). The
weatherhoods include 2-inch aluminum mesh filters that
are removed out of the end of the hood as shown in this
drawing and require extra clearance for removal.
Bypass
Damper
Face
Damper
Outdoor Air Hood
Filters
Filters
Filters
Exhaust
Air Hood
Control Center
Face/Bypass Damper
Plate Heat
Exchanger
Plate Heat
Exchanger
Outdoor
Air Hood
C
B
A
D
E
CLEARANCE
CLEARANCE
B
C
A
D
D
Do not face the Outdoor Air Intake of the unit into 
prevailing wind and also keep the air intake away 
from any other exhaust fans. Likewise, position the 
Exhaust Air Discharge opening away from any other 
outdoor air intakes of other equipment.
When cutting duct openings, cut opening one inch 
larger (25 mm) than duct size to allow clearance for 
installation. Area enclosed by roof curb must comply 
with clearance to combustible materials. If the roof 
is constructed of combustible materials, area within 
the roof curb must be ventilated, left open or covered 
with non-combustible material which has an “R” value 
of at least five (5). If area within curb is left open, 
higher radiated sound levels may result.
Where the supply or warm air duct passes through 
a combustible roof, a clearance of one inch must be 
maintained between the outside edges of the duct 
and combustible material in accordance with NFPA 
Standard 90A.
SA Discharge