Roof curb and rail mounting, Service clearances duct dimensions, Intake and discharge options – Greenheck Fan PVE-35 User Manual

Page 5: Bc a d d

Advertising
background image

5

Model PVe Heat Recovery Unit

When installed on a roof, a typical installation
will include at least one roof penetration in order
to deliver return air to the unit from the space.
Additionally, a second roof penetration may be used
for supply air discharge to the space.

Roof Curb and Rail Mounting

Service Clearances

Duct Dimensions

Position the unit roof opening such that the Return Air
Intake will line up with the corresponding ductwork.
If applicable, adjust position to also accommodate
the SA Discharge vent. Make certain that proposed
positioning of the unit still maintains recommended
service clearances.

Option

Bottom

Top

Side

End

OA Intake

X

SA Discharge

X

X

RA Intake

X

EA Discharge

X

OA - Outdoor Air

SA - Supply Air (to the space)

RA - Return Air (from the space)

EA - Exhaust Air

Model

A

B

C

D

E

F

PVe-20

10.7

(280)

12.2

(310)

10.3

(270)

11.8

(300)

22.0

(570)

14.0

(360)

PVe-35

11.9

(310)

13.7

(350)

11.4

(290)

13.1

(340)

34.0

(870)

14.0

(360)

PVe-45

14.1

(360)

16.0

(410)

13.3

(340)

14.5

(370)

46.0

(1170)

14.0

(360)

PVe-55

16.4

(420)

19.2

(490)

15.9

(450)

18.6

(480)

60.0

(1530)

14.0

(360)

All dimensions are shown in inches (millimeters).

Intake and Discharge Options

Bypass

Damper

Face

Damper

Outdoor Air Hood

Filters

Filters

Filters

Exhaust

Air Hood

Control Center

Face/Bypass Damper

Plate Heat

Exchanger

Plate Heat

Exchanger

Outdoor

Air Hood

C

B

A

D

E

CLEARANCE

CLEARANCE

B

C

A

D

D

OA Intake

RA Intake

SA Discharge

EA Discharge

B

A

C

D

E

F

Model

A

B

C

D

PVe-20

36

(920)

36

(920)

36

(920)

60

(1530)

PVe-35

48

(1220)

36

(920)

36

(920)

60

(1530)

PVe-45

60

(1530)

36

(920)

36

(920)

60

(1530)

PVe-55

72

(1830)

36

(920)

36

(920)

60

(1530)

All dimensions are shown in inches (millimeters). The

weatherhoods include 2-inch aluminum mesh filters that

are removed out of the end of the hood as shown in this

drawing and require extra clearance for removal.

Bypass

Damper

Face

Damper

Outdoor Air Hood

Filters

Filters

Filters

Exhaust

Air Hood

Control Center

Face/Bypass Damper

Plate Heat

Exchanger

Plate Heat

Exchanger

Outdoor

Air Hood

C

B

A

D

E

CLEARANCE

CLEARANCE

B

C

A

D

D

Do not face the Outdoor Air Intake of the unit into
prevailing wind and also keep the air intake away
from any other exhaust fans. Likewise, position the
Exhaust Air Discharge opening away from any other
outdoor air intakes of other equipment.
When cutting duct openings, cut opening one inch
larger (25 mm) than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof
is constructed of combustible materials, area within
the roof curb must be ventilated, left open or covered
with non-combustible material which has an “R” value
of at least five (5). If area within curb is left open,
higher radiated sound levels may result.
Where the supply or warm air duct passes through
a combustible roof, a clearance of one inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A.

SA Discharge

Advertising