Remote control panel and wiring schematics, Day timer or on/off switch, Hand/off/auto switch – Greenheck Fan PVE-35 User Manual

Page 16

Advertising
background image

16

Model PVe Heat Recovery Unit

Remote Control Panel and Wiring
Schematics

Indicator Lights powered by the ER Unit

Dirty Filter Indicator (power by others)

Refer to Pressure Switch for voltage and load ratings.

7-Day Timer or On/Off Switch

G

C

R

7-Day Timer

S1 - Unit On/Off

Terminal Block

in Unit

Control Center

For 7-Day Timer, use blue and black wires.
Red wires should be capped off.

G

C

R

On
Off

BMS

Auto

Terminal Block

in unit

Control Center

Hand/Off/Auto Switch

Hand/Off/Auto Switch allows the unit to

“Off” - off

“On” - Manual Operation

“Auto” - Unit is controlled by BMS, RTU, etc.
NOTE: RTU controllers are by others.

The remote panel is a series of junction boxes ganged
together and includes a stainless steel faceplate. The
remote panel is available with a number of different
alarm lights and switches to control the unit. The
remote panel ships loose and requires mounting and
wiring in the field
The remote panel is available with the following
options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Time delay override
• Economizer light
• Frost control light
• Exhaust air dirty filter light
• Outdoor air dirty filter light

Refer to Electrical Connections section for Field Control

Wiring recommendations.

W1

12

7

6

Y2

Y1

G

C

R

NC

C

NC

C

NO

NO

Exhaust Dirty Filter

Supply Dirty Filter

Economizer

PS2

PS3

Frost Control

Unit On/Off

NC

NC

NO

C

NO

C

Exhaust Dirty Filter

Supply Dirty Filter

Hot

L1

PS2

PS3

Advertising
This manual is related to the following products: