Routine maintenance, Maintenance procedures – Greenheck Fan PVE-35 User Manual
Page 23
 
23
Model PVe Heat Recovery Unit
Fan Belts
Belts must be checked on a regular basis for 
wear, tension, alignment, and dirt accumulation. 
Premature or frequent belt failures can be caused by 
improper belt tension (either too loose or too tight) 
or misaligned sheaves. Abnormally high belt tension 
or drive misalignment will cause excessive bearing 
loads and may result in failure of the fan and/or motor 
bearings. Conversely, loose belts will cause squealing 
on start-up, excessive belt flutter, slippage, and 
overheated sheaves. Both loose and tight belts can 
cause fan vibration.
When replacing belts on multiple groove drives, all 
belts should be changed to provide uniform drive 
loading. Do not pry belts on or off the sheave. Loosen 
belt tension until belts can be removed by simply 
lifting the belts off the sheaves. After replacing belts, 
insure that slack in each belt is on the same side of 
the drive. Belt dressing should never be used.
Do not install new belts on worn sheaves. If the 
sheaves have grooves worn in them, they must be 
replaced before new belts are installed.
The proper belt setting is the lowest tension at which 
the belts will not slip under peak load operation. For 
initial tensioning, set the belt deflection at 1/64-inch 
for each inch of belt span (measured halfway between 
sheave centers). For example, if the belt span is 
64 inches, the belt deflection should be one inch 
(using moderate thumb 
pressure at mid-point 
of the drive). Check 
belt tension two times 
during the first 24 hours 
of operation and 
periodically thereafter.
Fan Motors
Motor maintenance is generally limited to cleaning 
and lubrication. Cleaning should be limited to exterior 
surfaces only. Removing dust and grease buildup 
on the motor housing assists proper motor cooling. 
Never wash-down motor 
with high pressure spray. 
Greasing of motors is 
only intended when 
fittings are provided. 
Many fractional motors 
are permanently 
lubricated for life and 
require no further 
lubrication.
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death. 
Before attempting to perform any service or 
maintenance, turn the electrical power to unit 
to OFF at disconnect switch(es). Unit may have 
multiple power supplies.
CAUTION
Use caution when removing access panels or other 
unit components, especially while standing on a 
ladder or other potentially unsteady base. Access 
panels and unit components can be heavy and 
serious injury may occur.
Once the unit has been put into operation, a routine 
maintenance program should be set up to preserve 
reliability and performance. Items to be included in 
this program are:
Lubrication 
Apply lubrication where required
Dampers
Check for unobstructed operation
Fan Belts
Check for wear, tension, alignment
Motors
Check for cleanliness
Blower Wheel & Fasteners
Check for cleanliness 
Check all fasteners for tightness 
Check for fatigue, corrosion, wear
Bearings
Check for cleanliness 
Check set screws for tightness 
Lubricate as required
External Filter
Check for cleanliness - clean if required
Internal Filter
Check for cleanliness - replace if required
Door Seal
Check if intact and pliable
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication. 
Apply lubrication where required. Any components 
showing excessive wear should be replaced to 
maintain the integrity of the unit and ensure proper 
operation.
Dampers
Check all dampers to ensure they open and close 
properly and without binding. Backdraft dampers can 
be checked by hand to determine if blades open and 
close freely. Apply power to motorized dampers to 
ensure the actuator opens and closes the damper as 
designed.
Belt Span
Deflection = Belt Span
64