Factory set points, Continued – Greenheck Fan PVE-35 User Manual

Page 13

Advertising
background image

13

Model PVe Heat Recovery Unit

MODULATING CONTROL FOR FAN SPEED

(0-10 VDC)

Parameter

Setting

V1000

J1000

A1-01

Access Level

2

2

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H3-04

Terminal A1 Bias

50%

50%

A1-01

Access Level

0

0

MULTISPEED CONTROL FOR FAN SPEED

(1/3 OR 1/2 SPEED REDUCTION)

Parameter

Setting

V1000

J1000

A1-01

Access Level

2

2

b1-01

Reference Source (Frequency)

0

0

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

d1-01

Frequency Reference 1

60 Hz

60 Hz

d1-02

Frequency Reference 2

40 Hz

40 Hz

d1-03

Frequency Reference 3

30 Hz

30 Hz

d1-04

Frequency Reference 4

60 Hz

60 Hz

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H1-04

Multfunction Input Sel 4

(Terminal S4)

3

3

H1-05

Multifunction Input Sel 5

(Terminal S5)

4

4

H1-06

Multifunction Input Sel 6

(Terminal S6)

5

NA

H3-10

A2 Not Used

F

NA

A1-01

Access Level

0

0

CO2 SENSOR CONTROL FOR FAN SPEED

(1/2 SPEED WHEN C02 DROPS bELOW 700 PPM)

(FULL SPEED WHEN C02 RISES AbOVE 800 PPM)

Parameter

Setting

V1000

J1000

A1-01

Access Level

2

2

b1-01

Reference Source (Frequency)

0

0

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

d1-01

Frequency Reference 1

60 Hz

30 Hz

d1-02

Frequency Reference 2

30 Hz

60 Hz

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H3-10

A2 Not Used

F

NA

A1-01

Access Level

0

0

Factory Set Points -

continued

Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to “2”.
Then go to A1-03 and change it to “1110” and press
enter. The drive is now reset back to the settings
programmed at Greenheck. This option is not
available on the J1000.