Sensors mounted by factory – Greenheck Fan PVE-35 User Manual

Page 17

Advertising
background image

17

Model PVe Heat Recovery Unit

Temperature Sensors - 1K Ohm RTD

Drawing

Labels

Terminal Strip Labels

OAI

OA/Supply Inlet Temp

OAAP

OA After Plate Temp

RAI

RA/Exhaust Inlet Temp

EAP

Exhaust After Plate Temp

OAD

Supply Discharge Temp

Pressure Sensors (analog or digital)

Drawing

Labels

Terminal Strip Labels

OAF-P

OA Supply Filter Pressure

RAF-P

RA Exhaust Filter Pressure

EP-P

(2 sensors)

Exhaust Plate Pressure

OAP-P

(2 sensors)

Outdoor Air Plate Pressure

Amp - Current Sensors (analog or digital)

Drawing

Labels

Terminal Strip Labels

EF-A

Exhaust Fan Amps

OAF-A

Supply Fan Amps

Sensors Mounted by Factory

Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit
diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are
labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for
the controls contractor to connect the Building Management System for monitoring purposes.

OAAP

OAF-A

OAD

SUPPLY

BLOWER

TO

INSIDE

OAI

OA

FILTER

OAF-P

FROM

OUTSIDE

FROM

INSIDE

TO

OUTSIDE

PLATE

HEAT

EXCHANGER

EAP

EF-A

EXHAUST

BLOWER

RAI

RAF-P

RA

FILTER

OAP-P

EP-P