Optional accessories – Greenheck Fan PVE-35 User Manual
Page 11
 
11
Model PVe Heat Recovery Unit
Frost Control Application/Operation
Cold climates, in combination with higher indoor 
humidity levels, may cause frost to form on the plate 
heat exchanger. To protect against the formation of 
frost, a temperature sensor is installed to measure 
the temperature of the air leaving the plates in the 
exhaust airstream. There are three different methods 
of frost control that may optionally be used. These 
options are installed, wired and pre-set at the factory. 
To identify specific components, see the included 
unit-specific schematic wiring diagram.
 1. Timed Exhaust frost control
 The supply blower cycles on and off based on a 
factory provided and installed timer. The timer is 
located on the right hand side (low voltage side) 
of the control module.
 2. Plate heat exchanger bypass – Open/Closed
 When the exhaust air leaving the exchanger 
(cube) drops below the adjustable set-point, both 
the face and bypass dampers will allow air to 
bypass the cube. This allows warm exhaust air 
to melt any frost on the cube. Once the exhaust 
air temperature rises above the set-point, the unit 
returns to normal operation.
 3. Electric preheat frost control
 An electric preheater can optionally be built into 
the outdoor air intake. When the temperature 
of the exhaust air leaving the plate unit (the 
cube) drops below the adjustable set-point, the 
preheater will switch on. Once the exhaust air 
temperature increases, the preheater will switch 
off.
The typical temperature setting corresponds to the 
indoor air relative humidity as shown in the Frost 
Threshold Temperatures table and represents when 
frost can occur. An increase in pressure drop would 
indicate that frost is occurring. Both the pressure 
sensor AND the outdoor air temperature sensor 
must trigger in order to initiate frost control. The 
two sensors together insure that frost control is 
only initiated during a real frost condition. Field 
wiring of a light (or other alarm) between 6 & C in 
the control center will notify personnel when unit is 
in frost control mode (refer to Remote Panel Wiring 
schematics for wiring details). The following explains 
the three options in more detail.
Timed exhaust frost control includes a timer in 
addition to the thermostat and pressure sensor. The 
timer is located on the right hand side of the control 
module (low voltage side). When timed exhaust frost 
control is initiated, the timer will turn the supply 
blower on and off to allow the warm exhaust air 
to defrost the cube. Default factory settings are 
5 minutes off and 30 minutes on.
Plate (cube) bypass. The plate bypass frost control 
function is essentially the same as Economizer 
mode (see below) except that it is initiated by 
temperature sensors for the purpose of frost removal 
or prevention.
Electric preheat frost control includes an electric 
heater at the outdoor air intake, an airflow pressure 
switch and a temperature sensor. See also Electric 
Heater Application / Operation. When electric preheat 
frost control is initiated, the electric preheater will 
turn on and warm the incoming air to prevent frost 
accumulation on the cube.
Frost Threshold Temperatures
Indoor RH @ 70°F
Frost Threshold Temp
20%
-5º F
30%
-5º F
40%
-5º F
Optional Accessories
Economizer Application/Operation
Under certain conditions, the most efficient use of 
the PVe Heat Recovery Ventilator includes bypassing 
the incoming outdoor air around the plate heat 
exchanger. When cooling air is being called for and 
the outdoor air temperature is below a pre-set point, 
the PVe will switch to Economizer Mode. Integral 
face and bypass dampers will cycle into a bypass 
condition, allowing incoming cool air to flow past 
the cube, rather than flow through it. Economizer 
Mode is strictly temperature initiated and dependent 
on the Temperature Sensor with override located in 
the control center. See component #7 on the Typical 
Control Center Components illustration.