Greenheck Fan PVE-35 User Manual
Page 24
 
24
Model PVe Heat Recovery Unit
Fan Wheel & Fasteners
Wheels require very little attention when moving clean 
air. Occasionally oil and dust may accumulate on the 
wheel causing imbalance. When this occurs the wheel 
and housing should be cleaned to assure smooth and 
safe operation. Inspect fan impeller and housing for 
fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking 
collars on the fan, bearings, drive, motor base and 
accessories for tightness. A proper maintenance 
program will help preserve the performance and 
reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require 
no further lubrication under normal use. Normal use 
being considered -20ºF to 120ºF and in a relatively 
clean environment. Some bearings are relubricatable 
and will need to be regreased depending on fan use. 
Check your bearings for grease zerk fittings to find 
out what type of bearing you have. If your fan is not 
being operated under normal use, bearings should be 
checked monthly for lubrication.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the 
supply weatherhood (if the weatherhood option was 
purchased). Filters should be checked and cleaned 
on a regular basis for best efficiency. The frequency 
of cleaning depends upon the cleanliness of the 
incoming air. These filters should be cleaned prior to 
start-up.
Clean filters by rinsing with a mild detergent in warm 
water.
Internal Filter Maintenance
The PVe units are always provided with 2-inch, 
pleated filters in the outdoor air and exhaust 
airstreams. These filters should be checked per 
a routine maintenance schedule and replaced as 
necessary to ensure proper airflow through the 
unit. See table for pleated filter size and quantity 
for each unit. Replacement filters shall be of same 
performance and quality as factory installed filters. 
Filter type must be pleated design with integral metal 
grid. Two acceptable filter replacements are Aerostar 
Series 400 or Farr 30/30
®
.
Outdoor Air Filters: Access to the outdoor air filters 
is through the door labeled as “Filter Access” on the 
outdoor air side of the unit. 
Exhaust Air Filters: Access to the exhaust air filters 
is through the door labeled as “Filter Access” on the 
exhaust air side of the unit.
Refer to Access Door Descriptions section for 
additional information on filter locations.
Door Seal Maintenance
Slip-on type seal is installed on the door. Inspect at 
least annually to ensure that seal is still pliable and 
intact.
Filter Size and Quantities
Unit Size
Pleated Filter Size
Quantity
Supply and Exhaust
Supply
Exhaust
PVe-20
12 x 25 x 2
3
3
PVe-35
16 x 25 x 2
3
3
PVe-45
20 x 25 x 2
3
3
PVe-55
24 x 24 x 2
3
3
All dimensions in inches.