Dimensional data drain trap, Bc a d d – Greenheck Fan PVE-35 User Manual
Page 8
 
8
Model PVe Heat Recovery Unit
Dimensional Data
Drain Trap
Unit
Size
A
B
C
D
E
PVe-20
104.1
(2650)
59.7
(1520)
41.5
(1060)
20.3
(520)
20.7
(530)
PVe-35
104.1
(2650)
59.7
(1520)
49.2
(1250)
25.2
(640)
17.7
(450)
PVe-45
110.6
(2810)
59.7
(1520)
61.1
(1560)
25.2
(640)
19.0
(490)
PVe-55
116.5
(2959)
59.7
(1520)
76.1
(1940)
25.2
(640)
23.8
(610
)
All dimensions are shown in inches (millimeters). 
Door handles, hinges and other protrusions are not 
included in the dimensions above. Dimensions are
rounded up to the nearest .1 inch (2.54 millimeters).
Bypass
Damper
Face
Damper
Outdoor Air Hood
Filters
Filters
Filters
Exhaust
Air Hood
Control Center
Face/Bypass Damper
Plate Heat
Exchanger
Plate Heat
Exchanger
Outdoor
Air Hood
C
B
A
D
E
CLEARANCE
CLEARANCE
B
C
A
D
D
Top view
Bypass
Damper
Face
Damper
Outdoor Air Hood
Filters
Filters
Filters
Exhaust
Air Hood
Control Center
Face/Bypass Damper
Plate Heat
Exchanger
Plate Heat
Exchanger
Outdoor
Air Hood
C
B
A
D
E
CLEARANCE
CLEARANCE
B
C
A
D
D
Side view
The PVe plate heat exchanger is provided with two 
stainless steel drain pans and each is equipped with 
a one inch MPT drain fitting. A drain trap must be 
installed on each drain fitting to allow excess water 
to flow out of the drain pans. More importantly, 
though, due to the negative internal static pressure 
inside the PVe cabinet, installing drain traps prevents 
outdoor air from being pulled into the cabinet and 
consequently causing overfilling of the drain pans or 
misting of PVe components.
To ensure the drain trap works properly, the trap 
height must account for the difference in static 
pressure between ambient conditions outside the 
unit and the negative static pressure inside the PVe 
cabinet. An assumption of 3.0 in. wg differential is 
normally sufficient for all PVe units and this would 
require a trap design as shown. If the internal static is 
believed to be higher, consult the factory.
Refer to local codes to determine drainage 
requirements. If draining onto a roof, place a drip pad 
beneath the drain outlet to protect the roof. If draining 
onto a roof is not acceptable, a drain line must be 
attached to the drain trap. The drain line must be 
pitched away from the unit at least 1/8-inch per foot. 
On longer runs, an air break should be incorporated 
to ensure proper drainage. Local codes may require 
drainage into a waste water system.
Drainage problems result not only from improper 
drain trap design, but also from lack of maintenance 
in the PVe cabinet. Algae can form in the drain pans 
and traps and cause reduced water flow, which can 
in turn result in a backup in the drain system. Regular 
maintenance and inspection will prevent this from 
occurring. If the drains have a cleanout opening, be 
sure and close the opening after cleaning and refill 
the trap with water.
4 in.
2 in.