TALLY Command

The TALLY command has the form:

TALLY <task(s)>

where <task(s)> is one or more task identification letters from Table 5-3

This command causes the current value of the tallies for the specified task or tasks to be
displayed. Some of these tallies simply indicate load and performance information
about the station. Others can indicate whether or not there are problems either within
the station or within the network. See Chapter 5, Troubleshooting, for more information
on using the tallies to help isolate and resolve problems.

An example TALLY command is shown below:

> tally c

<<< PLC Driver Tallies >>>

PlcQFull = 0000H PlcSweep = 03c9H MsgRcv = 0038H PLCReq = 001aH

PlcAbt = 0000H MsgSent = 0036H MyAbt = 0000H Write = 0023H

Read = 0010H Timeout = 0000H Regs = 0400H AnInput = 0040H

AnOutput = 0040H uCode = 0300H

Table 5-11. PLC Driver Tallies (Tally c)

БББББББ

БББББББ

Tally

БББББББББББББББББББ

БББББББББББББББББББ

Meaning

БББББББ

БББББББ

PlcQFull

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of times a request of the PLC was retried be-
cause of congestion in the PLC.

БББББББ

БББББББ

БББББББ

PlcSweep

БББББББББББББББББББ

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of executive windows received by the Ethernet
Interface.

БББББББ

MsgRcv

БББББББББББББББББББ

Count of the number of messages received from the CPU.

БББББББ

БББББББ

БББББББ

PlcReq

БББББББББББББББББББ

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of COMMREQs received from the application
program.

БББББББ

PlcAbt

БББББББББББББББББББ

Count of the number of times the CPU aborted a data transfer.

БББББББ

БББББББ

MsgSent

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of messages sent to the CPU.

БББББББ

БББББББ

MyAbt

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of times the Ethernet Interface aborted a data
transfer.

БББББББ

БББББББ

БББББББ

Write

БББББББББББББББББББ

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of times the Ethernet Interface successfully
wrote to the PLC memory.

БББББББ

БББББББ

Read

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of times the Ethernet Interface successfully read
from the PLC memory.

БББББББ

БББББББ

Timeout

БББББББББББББББББББ

БББББББББББББББББББ

Count of the number of times the Ethernet Interface timed out wait-
ing for a response from the CPU.

БББББББ

БББББББ

uCode

БББББББББББББББББББ

БББББББББББББББББББ

The microcode revision level of the firmware in the CPU.