The operational state, Troubleshooting when status ok led is off – GE GEFanuc Automation Programmable Control Products TCP/IP Ethernet Communications for the Series 90t-70 PLC GFK-1004B User Manual

Page 179

Advertising
background image

6

6-8

TCP/IP Ethernet Communications User’s Manual – January 1996

GFK-1004B

The Operational State

The Operational State is the state of normal operation of the Ethernet Interface. This
section identifies the possible symptoms of problems which may occur while the module
is operating.

During normal operation of the Ethernet Interface, the MODULE OK LED is ON. The
other two LEDs (ONLINE, STATUS OK) provide information about the health of the
Ethernet Interface and activity on the LAN. The table below shows the LED patterns
you might see and their possible meanings.

In the Operational State, no “. . . Utility” message follows the station ID in the NODE
command. The prompt character at the local Station Manager terminal is a greater-than
symbol (“>”).

Table 6-6. Operational State

БББББББББ

БББББББББ

БББББББББ

LED

БББББББББББ

БББББББББББ

БББББББББББ

Connected to LAN

БББББББББ

БББББББББ

БББББББББ

Not Connected to LAN

БББББББББ

БББББББББ

БББББББББ

LED

ББББББ

ББББББ

ББББББ

Operating w/o

Exceptions

ББББББ

ББББББ

ББББББ

An Exception
has Occurred

БББББББББ

БББББББББ

БББББББББ

Not Connected to LAN

БББББББББ

БББББББББ

MODULE OK

ББББББ

ББББББ

ON

ББББББ

ББББББ

ON

БББББББББ

БББББББББ

ON

БББББББББ

БББББББББ

ONLINE

ББББББ

ББББББ

ON/Blink

1

ББББББ

ББББББ

ON/Blink

1

БББББББББ

БББББББББ

OFF

БББББББББ

БББББББББ

STATUS OK

ББББББ

ББББББ

ON

ББББББ

ББББББ

OFF

2

БББББББББ

БББББББББ

OFF

2

1. ONLINE blinking indicates this node is sending or receiving data.
2. When MODULE OK is ON and STATUS OK is OFF, it is necessary to use the Station Manager

NODE, LOG, and SOSW commands to distinguish among the possible causes.

Troubleshooting When STATUS OK LED is OFF

If the Ethernet Interface is in the Operational State and the STATUS OK LED is OFF and
the MODULE OK LED is ON, then the Ethernet Interface has detected an exception
condition and has made an entry in the Exception Log. Each new (not repeating) log
event is also sent to the PLC Fault Table, where it can be viewed using Logicmaster 90-70
Software.

The format of a log event as displayed by the Station Manager is shown below:

Entry

Date Time Event Count 1 2 3 4 5 6

dd-mmm-yyyy hh:mm:ss.s xx xxxx xx xxxx xxxx xxxx xxxx xxxx

Date

- The Date column contains the system date of the last occurrence of the logged

event.

Time

- The Time column contains the system time of the last occurrence of the logged event.

Event

- The Event column gives the kind of event which occurred. Table 6-9 and 6-10

lists the possible values for events.