The field network test state – GE GEFanuc Automation Programmable Control Products TCP/IP Ethernet Communications for the Series 90t-70 PLC GFK-1004B User Manual

Page 177

Advertising
background image

6

6-6

TCP/IP Ethernet Communications User’s Manual – January 1996

GFK-1004B

The operator must correct the fault forcing entry into this state before the Ethernet
Interface may proceed. In most cases this may be done by using the Logicmaster 90-70
Configurator or the Station Manager CHSOSW command. It cannot be performed
remotely from the network. After entering new Soft Switch information or correcting
another fault, the Ethernet Interface must be restarted to begin using these new values.

In the Soft Switch Entry state, a NODE command to the Station Manager will yield a
“Soft Switch Entry Utility” message following the station identification information; also,
the Station Manager prompt is an asterisk (“*”).

Table 6-3. Soft Switch Entry State

БББББББ

БББББББ

LED

БББББББББ

БББББББББ

Soft Switch Entry State

БББББББ

БББББББ

MODULE OK

БББББББББ

БББББББББ

Slow Blink

БББББББ

БББББББ

ONLINE

БББББББББ

БББББББББ

OFF

БББББББ

БББББББ

STATUS OK

БББББББББ

БББББББББ

OFF

Slow Blink = Blink ON every 2 seconds.

The Field Network Test State

The Field Network Test state is selected by entering a “F” or “f ” in response to the “@”
prompt at the local Station Manager terminal at the end of power-up diagnostics. The
“f ” will not be echoed back. A limited subset of Station Manager commands is provided
in this state. Refer to Chapter 5, “Field Network Test Utility” for a detailed description of
the Field Network Test state and to Chapter 2, “Installation Procedure 5 - Testing the
Ethernet Interfaces on the Network” for an application. The table below shows the LED
patterns for Field Network Test State.

In the Field Network Test State, a NODE command to the Station Manager will indicate
“Field Network Test Utility”. The Station Manager prompt is a dollar sign (“$”).

Table 6-4. Field Network Test State

БББББББББ

БББББББББ

LED

БББББББББББ

БББББББББББ

Connected to LAN

БББББББББ

БББББББББ

Not Connected to LAN

БББББББББ

БББББББББ

БББББББББ

LED

ББББББ

ББББББ

ББББББ

Operating w/o

Exceptions

ББББББ

ББББББ

ББББББ

An Exception
has Occurred

БББББББББ

БББББББББ

БББББББББ

Not Connected to LAN

БББББББББ

БББББББББ

MODULE OK

ББББББ

ББББББ

ON

ББББББ

ББББББ

ON

БББББББББ

БББББББББ

ON

БББББББББ

БББББББББ

ONLINE

ББББББ

ББББББ

ON/Blink

1

ББББББ

ББББББ

ON/Blink

1

БББББББББ

БББББББББ

OFF

БББББББББ

STATUS OK

ББББББ

ON

ББББББ

OFF

2

БББББББББ

OFF

2

1. ONLINE blinking indicates this node is sending or receiving data.
2. When MODULE OK is ON and STATUS OK is OFF, it is necessary to use the Station Manager

NODE, LOG, and SOSW commands to distinguish among the possible causes.