Gas-Fired Products Infrared Radiant Tube Heater PTS Series User Manual

Page 36

Advertising
background image

Form #43343330

May 08

–35–

SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)
1. When venting the heater to outside of building through a roof, use single-wall metal pipe. This is to be

constructed of galvanized sheet metal or other approved noncombustible corrosion-resistant material as
allowed by state or local codes.

2. A vent passing through a combustible roof shall extend through an approved clearance roof thimble.

Double-wall, Type B vent must be used for the portion of the vent system which passes through the roof. An
approved vent cap (Leslie “VersaCap”-Type B or equal) must be attached to end of the flue.

3. The maximum equivalent length of vent pipe should be carefully observed. A safety switch in the heater is

designed to shut the heater off before excessive flue restriction causes bad combustion. Refer to the Vent
Sizing Table for maximum vent lengths and vent pipe diameter.

4. Joints between sections of piping shall be fastened by sheet metal screws or other approved means and

should be sealed to prevent leakage of flue gas into building. Aluminum or Teflon tape suitable for 550ºF
(3M Company tapes 433 or 363) or silicone sealant is recommended.

5. All portions of the vent pipe shall be supported to prevent from sagging (6’ spacing is recommended).
6. When the vent pipe passes through areas where the ambient temperature is likely to induce condensation of

the flue gases, the vent pipe should be insulated and a condensation drain should be provided.

7. Minimum clearance for single-wall flue pipe to combustible material shall be 6 inches. This may be reduced

when the combustible material is protected as specified in the National Fuel Gas Code or the authority
having jurisdiction.

8. Single-wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass

through any attic, inside wall or concealed space, or through any floor. For the installation of a single-wall
metal pipe through an exterior combustible wall, refer to latest edition of the National Fuel Gas Code or the
authority having jurisdiction.

9. A venting system shall terminate at least 3 ft. above any forced air inlet located within 10 ft.


SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)
When venting the heater horizontally through a combustible outside sidewall, the same requirements listed
previously for venting Vertical Through The Roof apply except as follows:
1. A vent passing through a combustible wall must pass through an approved clearance thimble (Air-Jet #4VT

or Ameri-Vent #4EWT or other thimbles that are listed by a nationally recognized testing agency.

2. An approved vent cap (Breidert-Type L or equal) must be attached to the end of the vent pipe.
NOTE: To minimize problems associated with condensation in long horizontal runs, vent pipe can be insulated.
3. Use the following correction factors to obtain the equivalent length when elbows are used:

c. Subtract 10 ft. for each elbow beyond 15 ft. from the heater.

d. Subtract 15 ft. for each elbow within 15 ft. of the heater.

4. Limit to (2) 90º elbows in the vent system.
5. When venting through a sidewall, the horizontal vent pipe shall fall not less than 1/2 inch per 20 feet from

the start of the vent system to the vent terminal. All portions of the vent pipe shall be supported to prevent
sagging. (6’ spacing is recommended)

6. A minimum clearance of 6 inches must be maintained between the outside wall and vent cap.

Vent Cap (Leslie

VersaCap Type B)

Flashing

2” (5cm)

Clearance

Thimble

Seal Joint

and Annular

Space

10 ft (305cm)

or less

2 ft (77cm)

minimum

2 ft (77cm) minimum

(when no wall or

parapet exists)

4” Diameter

Vent

W

all or

Parapet

Flue Adapter

Collar

4” Vent Elbow

#10 Self-Drill

Screws

(typical)

4” Vent Pipe

(vertical position)

Advertising
This manual is related to the following products: