Gas-Fired Products Infrared Radiant Tube Heater PTS Series User Manual

Page 38

Advertising
background image

Form #43343330

May 08

–37–


Multiple Heater Vertical venting arrangement.

Total

Vent

Height

Vent Cap (Leslie

VersaCap Type B)

Flashing

2” (5cm)

Clearance

Thimble

Seal Joint

and Annular

Space

10 ft (305cm)

or less

2 ft (77cm)

minimum

2 ft (77cm) minimum

(when no wall or

parapet exists)

4” Diameter

single wall Vent

W

all or

Parapet

See multiple

vent size table

for diameter

Flue Collar

adaptor

Connections to the common vent

must be arranged to avoid direct

opposition of exhaust products.

Plan View

Multiple Heater Horizontal venting arrangement.

4” Diameter

single wall Vent

Flue Collar

adaptor

Plan View

Vent Cap

(Breidert or

equivalent Type L)

2” (5cm)

Clearance

Thimble

1/2” (12mm) fall per 20 ft

(6m) toward vent terminal

6” (15cm)

minimum

Swept Tee

4” Diameter

single wall Vent

Flue Collar

adaptor

2” (5cm)

Clearance

Thimble

1/2” (12mm) fall per 20 ft

(6m) toward vent terminal

6” (15cm)

minimum

Swept Y

See multiple

vent size table

for diameter

See multiple

vent size table

for diameter

VENT SIZING TABLE — Multiple Heater Venting

Number of Heaters

Horizontal and vertical

Vertical Only

1 2 3 4

PTS/PTU 40

4”

4”

4”

4”

PTS/PTU 50

4”

4”

4”

5”

PTS/PTU 75

4”

4”

5”

6”

PTS/PTU 100

4”

5”

6”

6”

PTS/PTU 125

4”

5”

6”

7”

PTS/PTU 150

4”

6”

7”

7”

PTS/PTU 175

4”

6”

7”

8”

PTS/PTU 200

4”

6”

7”

8”

COMMON VENT DIAMETER

(If a size is not available use the next larger size.)