In multiple heater applications, the combustion air intake may be ducted individually or common ducted in the same
configuration as shown for venting in Section 16.0. For combustion air intake duct sizing, please refer to the Vent
Sizing Table and use the diameter indicated, based on the number of heaters per duct.





Flue vent termination

must be 1 ft. (30 cm)

higher than combustion

air inlet cap.

Combustion

Air Intake

SIDE VIEW

(straight configuration)

Combustion Air Cap

(Leslie VersaCap

Type B)

4” Diameter

Single-Wall Pipe

Flashing

1/4” (6mm)

per ft. slope downwards

towards vent terminal

Horizontal

Through Sidewall

6” (15cm)

Minimum

4” Starting Collar

Burner Box

(side view)

3 ft. (91cm)

Minimum

4” Flexible Air Inlet Hose

2 Ft. Long

(Part No. 30675020)

4” Spring

Tension Clamp (2 each)

(Part No. 30676040)

Vertical

Through the roof