0) minimum clearances to combustibles – Gas-Fired Products Infrared Radiant Tube Heater PTS Series User Manual

Page 5

Advertising
background image

Form

#43343330

–4–

May 08

4.0)

MINIMUM CLEARANCES TO COMBUSTIBLES

Failure to do so may result in death, serious injury or

property damage.

Combustible material must be located outside the

clearance dimensions listed.

Minimum clearances to combustibles shall be measured from the outer surfaces as shown in the following diagram:





MINIMUM CLEARANCES TO COMBUSTIBLES

Mounted Horizontally

Angle Mounted at

45º

Model No.

Sides Ceiling*

Below

Ends

45º Front 45º Rear

PTS/PTU

40

27” 6” 40” 30” 48” 12”

PTS/PTU

50

27” 6” 40” 30” 48” 12”

PTS/PTU 75

27”

6”

60”

30”

48”

12”

PTS/PTU 100

66”

6”

88” **

40” 66” 20”

PTS/PTU 125

66”

6”

101” **

40” 66” 20”

PTS/PTU 150

84”

6”

106” **

48” 84” 24”

PTS/PTU 175

84”

6”

106” **

48” 84” 24”

PTS/PTU 200

84”

6”

106” **

48” 84” 24”

* When used indirect vented, minimum clearance for CEILING must be: 12” for PTS/PTU 50-75 and 18” for
PTS/PTU 100-200. If optional corner and u-bend reflectors are not used, the clearance must be 18”.

** Maximum clearance below reduces to 72” once you are 20ft. downstream from the control box.

WARNING: Certain materials or objects, when stored under the heater, will be subjected to radiant heat and

could be seriously damaged. Observe the Minimum Clearances to Combustibles listed in the manual and on the
heater at all times.

NOTE: The clearances specified above must be maintained to combustibles and other materials that may be
damaged by temperatures 90ºF above ambient temperature. Clearances to combustibles are posted on the
control box. In areas used for storage of combustible materials where they may be stacked below the heater,
NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height to
maintain the required clearances from the heater to combustibles.” Space-Ray recommends posting these signs
adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.

End

End

Ceiling

Below

Front

Rear

45° Angle (Maximum)

* Ceiling

Below

Side

Side

Horizontal